Pull cables
Check cable type, size and maximum distances
Pull cables for all inputs and outputs
Check device power requirements
Cable distance
Cable type
Cable format*
Single HBUS device – data only
Single HBUS device – data and power
Multiple HBUS devices – data only
Multiple HBUS devices – data and power
CAT 5e or better**
4 twisted pair Each 2 x 0.2 mm2 (24 AWG)
500 m (1640 ft)
50 m (165 ft)
500 m (1640 ft)
50 m (165 ft)
SEC472
4 x 0.2 mm2 Not twisted pairs (24 AWG)
400 m (1310 ft)
50 m (165 ft)
–
–
SEC4142
4 x 0.4 mm2 Not twisted pairs (21 AWG)
400 m (1310 ft)
100 m (330 ft)
–
–
* The matching of wire sizes to equivalent wire gauges are only approximate. ** Recommended cable types for optimal HBUS RS485 performance.
Shielded cable may reduce the obtainable cable length. Shielded cable should be grounded at the Controller end only.