F Series Fence Controllers communications advisory — February 2020

Review the F Series lightning diverter change for affected controller installations.

What happened

Monitored pulse fences have the potential for coupling between the conductive circuits, mainly when operating in dual pulse configuration. The coupling effect can be amplified where there is minimal separation between wires or fence structure.

Sparking caused by short circuiting or voltage leakage can lead to a high voltage pulse in excess of 16kV being received back at the fence controller. Pulses exceeding 16kV result in arcing from the inside of the fence controller through the internal lightning diverter. Arcing creates a high-frequency pulse capable of travelling through the components, leading to disruptions and potential damage to the RS485 communication lines for HBUS and LV synchronisation.

What Gallagher did

Following investigation and extensive testing, Gallagher determined the internal lightning diverter should be removed from all future production of fence controllers. All existing stock in Gallagher warehouses was reworked.

The absence of the internal lightning diverter has no adverse effect on product performance.

What to do on existing sites

For existing sites experiencing RS485 communications issues (HBUS and/or LV Sync):

  1. Check all fence controllers on site to ensure the lightning diverter has been removed. If it is still installed, remove the lightning diverter as the first step.

  2. Check the RS485 communication ports for potential damage.

Fence controllers with a serial number later than 1823xxxxxx were manufactured without the lightning diverter, so there is no need to check these on site.

A technical guide with R&D-recommended testing and diverter-removal instructions is available on the support site.

⚠️ Note: the internal lightning diverter is a legacy design from early-generation products. Its removal does not impact the lightning resistance of the product, nor does it replace the need for external lightning protection to be installed.

Contact: Dave Solly, Product Manager - Perimeter Systems, dave.solly@gallagher.com.