Wiegand overview

Understand Gallagher Wiegand connectivity, protocol behavior, pull-up resistors, and device wiring.

What hardware provides Wiegand connectivity to Command Centre?

Wiegand connectivity to Gallagher Command Centre can be achieved via the following hardware:

  • 3000 Controller (legacy product)

  • Controller with a 4R or 8R plug-in module

  • A GBUS URI (Standard or Wiegand)

  • An 8 In 2 Out Door Module Wiegand Variant


How does the Wiegand protocol work, and when are pull-up resistors needed?

Wiegand is an open-collector protocol. The D0 and D1 lines are pulled high and the Wiegand device pulls them low to send data.

Voltage reference: The voltage reference for Wiegand is typically 5V. Check the Wiegand device's specifications for exact voltage requirements.

Voltage swing / deviation: Wiegand signals require a sufficient voltage swing to be read reliably. Noise or impedance issues on long cable runs can cause inconsistent reads.


Pull-up resistors

How do I know if pull-up resistors are required?

If you are getting inconsistent data from the Wiegand device, pull-up or pull-down resistors on the D0 and D1 lines may be required.

How do I add pull-up resistors?

Add pull-up resistors between the D0/D1 lines and the supply voltage rail. Consult the Wiegand device documentation for recommended resistor values. Gallagher Technical Support can advise on specific configurations.

Pull-up resistors on the D0 and D1 lines

How are a Wiegand device and a Gallagher device connected?

Standard connections:

  • D0 and D1 convey the card data.

  • R out 1 pulls down the LED line to indicate an Access Granted event on the Wiegand device.

  • R out 2 pulls down the Buzzer line to indicate an Access Denied event.

⚠️ Ground is common between the Gallagher and Wiegand hardware. Power can be supplied externally, but the ground link between the two devices must be present.

After a valid credential is processed:

  • R out 1 (LED) pulses on for door access time (default: 5 seconds).

  • R out 2 (Buzzer) will pulse once.

After an invalid credential is processed:

  • R out 1 (LED) will do nothing.

  • R out 2 (Buzzer) will trigger on for the door access time (default: 5 seconds).