Wiegand overview
Understand Gallagher Wiegand connectivity, protocol behavior, pull-up resistors, and device wiring.
What hardware provides Wiegand connectivity to Command Centre?
Wiegand connectivity to Gallagher Command Centre can be achieved via the following hardware:
3000 Controller (legacy product)
Controller with a 4R or 8R plug-in module
A GBUS URI (Standard or Wiegand)
An 8 In 2 Out Door Module Wiegand Variant
How does the Wiegand protocol work, and when are pull-up resistors needed?
Wiegand is an open-collector protocol. The D0 and D1 lines are pulled high and the Wiegand device pulls them low to send data.
Voltage reference: The voltage reference for Wiegand is typically 5V. Check the Wiegand device's specifications for exact voltage requirements.
Voltage swing / deviation: Wiegand signals require a sufficient voltage swing to be read reliably. Noise or impedance issues on long cable runs can cause inconsistent reads.
Pull-up resistors
How do I know if pull-up resistors are required?
If you are getting inconsistent data from the Wiegand device, pull-up or pull-down resistors on the D0 and D1 lines may be required.
How do I add pull-up resistors?
Add pull-up resistors between the D0/D1 lines and the supply voltage rail. Consult the Wiegand device documentation for recommended resistor values. Gallagher Technical Support can advise on specific configurations.

How are a Wiegand device and a Gallagher device connected?
Standard connections:
D0 and D1 convey the card data.
R out 1 pulls down the LED line to indicate an Access Granted event on the Wiegand device.
R out 2 pulls down the Buzzer line to indicate an Access Denied event.
⚠️ Ground is common between the Gallagher and Wiegand hardware. Power can be supplied externally, but the ground link between the two devices must be present.
After a valid credential is processed:
R out 1 (LED) pulses on for door access time (default: 5 seconds).
R out 2 (Buzzer) will pulse once.
After an invalid credential is processed:
R out 1 (LED) will do nothing.
R out 2 (Buzzer) will trigger on for the door access time (default: 5 seconds).