Cannot add more Salto doors to a cardholder or access group
Resolve Salto card door limits and native-mode resync failures for access groups and deleted doors.
The per-card limit
The error "too many salto doors applied to this cardholder" appears because access lives on the card, which has limited space. A card can only hold so many doors: a default 512-byte config caps at about 96 Salto doors or Zones (this is not fixed). Workaround: use Salto Zones to group doors into one item. Command Centre cannot reliably warn before the limit, because checking would hurt performance.
Resync failures
A Salto Native (Mode 2) resync aligns Command Centre to Salto Space exactly. One object that cannot be processed stops the whole resync. Always confirm the exact Command Centre version, because limits and error verbosity vary.
Too many Salto doors on an Access Group (most common)
Exceeding the max access points per Access Group fails the resync (vEL9.40+): "ShipError 4 - Max number of locks and zones exceeded".

On v9.20 MR3 / v9.30 MR1+, the log names the FT Item (for example 601). On older versions, manually find the Access Group with more than 96 Salto doors. Fix: in the Configuration Client, use the Find Tool with [[<FTItemID>] in the Description field, de-associate the Access Group from the Salto doors, then create a Salto Zone with those doors and add the Zone to the Access Group.

A Zone groups access points into one item. It also saves key memory (about 230 bytes max) by storing one zone-entry permission instead of many individual ones.
Salto Space licence causing resync failure (Native mode)
Sites should run the SPAINT licence Gallagher generates (a SPABASIC/SPAIDSYS licence must be changed to SPAINT). The log shows SaltoCommunicator.cpp ... Unspecified error (80004005). Features required for Salto Native mode: SHIP, Partitions, Lockdown, Automatic Key Assignment, and Card Printing.

Deleted door sync issue
When a door is deleted in one system and a resync is run, Command Centre may keep showing the old door and the resync fails with C13A0052: This item cannot be deleted as it is assigned to an Access Group (then c13a001d The Salto Re-sync failed, or the partial-success variant c13a0050). The Write <n> value in the log identifies the door's FTItemID. Fix: use the Find Tool by FTItemID, remove the Access Group's access to the Salto door(s), Resync, then verify (include deleted items).