CU42E0 controller

Understand CU42E0 controller functions and configure its network address.

The CU42E0 is the Salto master door controller (2 onboard doors, plus an auxiliary CU42E0/CU4EB8 for lift, floor, and alarm).

CU42E0 controller board layout: 12V input, BUS485, TAMPER, READER 1/2, RL1-4, Ethernet, CLR button

Addressing

To manually address the CU42E0:

  1. Press CLR to detect readers.

  2. The CU42E0 is DHCP-ready. If DHCP is not available, set a static IP via a browser.

  3. Press CLR for 5 seconds for addressing mode (the LED blinks orange).

  4. Browse to 192.168.0.234, set the network parameters, then Send.

Use SALTO ProAccess to detect the device. The device must be in tamper to configure it.