MorphoWave and Sigma reader faults
Find possible solutions for common MorphoWave and Sigma reader faults.
The fault-finding tables for each reader, as given. The two tables are the same apart from the reader name, except that the Sigma table adds lines to "Reader is offline", "Not working properly" and "Enrollment Terminated". "CCFT service" is the Command Centre service; "MBTB" is MorphoBioToolBox.
MorphoWave
Morphowave Reader is offline
*Ping if the reader is able to response, if it's able to ping check the controller and make sure its online. *Check the port (Default 11010) *Check the "On-demand security State" *No Morpho readers in Command Centre license file *Wrong firmware on reader - Factory Sigma Readers with firmware 4.5.1 or 4.5.2 default to MA5G mode. Sites using Command Centre versions older than vEL7.80 will need to change the MA Sigma, MA Sigma Lite Reader firmware to MA2G.4.5.1(Legacy Mode) or MA Sigma Lite Plus Reader firmware to MA2G.4.5.1(Legacy Mode) firmware. *Network wiring incorrect *The command centre cannot communicate with this reader : Either need to recreate reader,
Morphowave Readers - Pending update
*Make sure morpho reader is online *Reboot morpho reader *Make sure Comman Centre and Controller are both compatible *Restart CCFT service
Morphowave Readers - Unable to communicate
*Check if the reader is able to response *Check the port *Check the "Security State" *Check the firmware compatibility *Factory Reset and Reconfigure of the reader
Morphowave Readers - Not working properly
*Check wiring connection *Restart/Reboot the reader *Restart the controller *Restart the CCFT service *Factory reset and re-configure of the reader *Enrollment reader locks up - No dongle *Reader generates "Input parameters are not valid" errors in the Trace Log file - Insufficient power to the reader *Reader appears to be working, but: • ‘Access Denied’ tone sounds, • the door opens, and • an ‘Access Granted’ event is generated. - Incorrect wiring *You get the error message "The selected permitted card technology settings are not supported by the biometric reader" when setting permitted card technologies on the Card Reader properties. - If you attempt to set a morpho reader to follow the site default, but the site default does not allow either of the card technologies that the morpho reader does (MIFARE Classic or DESFire). *Reader generates “Re-sync Access Failed” or “Updating the configuration failed” alarm, and shows “The reader has rejected some configuration and a firmware update may be required to ensure correctterminal behaviour” in the status - Wrong firmware on reader
Card not working on Morphowave
*No Morpho biometric is added in card type *No Morpho object added in card layout *Incorrect Facility Code *Card is in default site key *Biometric Authentication Rule (Disable) - From Morphowave webserver
Morphowave Readers - Unable to access web interface
*Morphowave will disable access web interface once get connected to Command Centre.In order to access again web interface, you need to "Enable Web Server" via Morphowave reader properties-Status and Overrides.
Morphowave Readers - Enrollment Terminated
*Unable to register fingerprints, might need to check Morphowave reader.
Morphowave Readers - Yellow Flash state
*Morphowave is online but unable to update, perform a factory reset thru MBTB or hard factory reset, restart ccft service manager, then push config and resync database. You can do include also to assign morphowave reader to a door. This should solve the issue.
Sigma
Sigma Reader is offline
Ping if the reader is able to response, if it's able to ping check the controller and make sure its online. Check the port (Default 11010) Check the "On-demand security State" No Morpho readers in Command Centre license file Wrong firmware on reader - Factory Sigma Readers with firmware 4.5.1 or 4.5.2 default to MA5G mode. Sites using Command Centre versions older than vEL7.80 will need to change the MA Sigma, MA Sigma Lite Reader firmware to MA2G.4.5.1(Legacy Mode) or MA Sigma Lite Plus Reader firmware to MA2G.4.5.1(Legacy Mode) firmware. Network wiring incorrect The command centre cannot communicate with this reader : Either need to recreate reader, Factory reset of the controller, check wiring connection Sigma lite reader shows offline in hardware tree but able to get event when access granted and able to ping: Restart the server
Sigma Readers - Pending update
Make sure sigma reader is online Reboot sigma reader Make sure Command Centre and Controller are both compatible Restart CCFT service
Sigma Readers - Unable to communicate
Check if the reader is able to response Check the port Check the "Security State" Check the firmware compatibility Factory Reset and Re-configure the reader
Sigma Readers - Not working properly
Check wiring connection Restart/Reboot the reader Restart the controller Restart the CCFT service Factory reset and re-configure of the reader Enrollment reader locks up - No dongle Reader generates "Input parameters are not valid" errors in the Trace Log file - Insufficient power to the reader Reader appears to be working, but: • ‘Access Denied’ tone sounds, • the door opens, and • an ‘Access Granted’ event is generated. - Incorrect wiring You get the error message "The selected permitted card technology settings are not supported by the biometric reader" when setting permitted card technologies on the Card Reader properties. - If you attempt to set a morpho reader to follow the site default, but the site default does not allow either of the card technologies that the morpho reader does (MIFARE Classic or DESFire). Reader generates “Re-sync Access Failed” or “Updating the configuration failed” alarm, and shows “The reader has rejected some configuration and a firmware update may be required to ensure correctterminal behaviour” in the status - Wrong firmware on reader "Reader error code 3" - Reader is online and updated database, but unable to read the fingerprint. : Could be a scan mismatch, networking wiring terminated, restart ccft service, firmware, factory reset controller and upgrade firmware to match cc. "Biometric Mismatch" - If this was logged and visible to Morpho Biotoolbox, -One issue we have observed is that when users are unfamiliar with enrolling fingerprints on the MSO1300, the fingerprint may be enrolled at a 180-degree orientation. In this case, the fingerprint is technically enrolled but will never be recognized.-Biometric Authentic Rule set to 1 -Check wiring termination, cabling and pin terminal
Card not working on Sigma
No Morpho biometric is added in card type No Morpho object added in card layout Incorrect Facility Code Card is in default site key Biometric Authentication Rule (Disable) - From Morpho webserver
Sigma Readers - Unable to access web interface
Morphowave will disable access web interface once get connected to Command Centre.In order to access again web interface, you need to "Enable Web Server" via Morphowave reader properties-Status and Overrides.
Sigma Readers - Enrollment Terminated
Unable to register fingerprints, might need to check Morpho reader. Ensure Enrollment reader is readable from windows, reinstall mso drivers.
Sigma Readers - Yellow Flash state
Morpho is online but unable to update, perform a factory reset thru MBTB or hard factory reset, restart ccft service manager, then push config and resync database. You can do include also to assign morphowave reader to a door. This should solve the issue.
MSO1300 cannot register a fingerprint in the Command Centre client
Make sure the driver is installed (use the driver installer from the ISO file), and update the driver from Device Manager.
Registering gives "Unable to enable duplicate detection as the licensing dongle does not support duplicate checking": untick the setting in the Morpho Biometric Card Type; restart the CCFT service; unplug and replug the device, and restart Windows.