IDEMIA reader does not come online after an update
Resolve IDEMIA Sigma reader failures after a mode change, database resynchronization, or firmware upgrade.
Sigma reader will not come back online after a mode change or database resync (pre-2020 hardware)
In 2018, a Gallagher site had issues with certain Sigma readers connected to Gallagher hardware. If a Sigma reader (Lite, Lite Plus or Multi) had its mode changed or its database resynced, the reader rebooted but did not come back online in Command Centre. Power cycling the reader resolved it. IDEMIA, the manufacturer of Sigma readers, worked with Gallagher on a temporary fix until a Sigma hardware redesign.
Cause: on pre-2020 hardware, the D0/D1 lines going into the reader stopped the reader power-cycling correctly.
Fix: fit 2 inline isolating diodes (1N4007) on the D0/D1 lines going to the Sigma reader, as pictured.

To confirm D0/D1 wiring, see the related page Wire IDEMIA readers over Wiegand, which also has the Morpho wiring videos.
Reader will not come online after a firmware upgrade
The firmware 11-10-2022 release changed the configuration to enforced secure. New or upgraded readers will not come online and cannot connect via MBTB 4.6.12 or lower. Use the On-Demand Security procedure to recover an enforced-secure reader. Enable On-Demand Security explains how to put a Morpho reader into the On-demand Security state. More detail is on IDEMIA reader cannot connect after the October 2022 firmware update.
Last updated