An IDEMIA reader does not work while others with the same setup do

Copy the configuration from a working IDEMIA reader to readers that do not work.

Sometimes a Morpho reader's configuration is not at its default for some reason: some readers will not work while others work fine, possibly because of a configuration setting in the reader. Work around it by downloading the configuration from a working reader with MBTB (Bio Toolbox) and uploading it to the reader(s) that are not working.

Copy the configuration from a working reader

  1. In Command Centre, open the working reader's properties. On Status and Overrides, select Enable Web Server for long enough to connect and download the configuration, then click Override Now.

    MA SIGMA Lite Reader Properties, Status and Overrides: Override Enable Web Server, for 1 hour, Override Now
  2. Open MBTB and connect to the reader's IP address.

    MBTB Connection: Terminal Type MA Sigma Family, TCP/IP, IPv4, port 11010 (the address is covered)
  3. Go to the second tab down (it looks like a reader) and click Save. A dialog asks where to save the reader's configuration. Enter a description and save.

    MBTB Manage Configuration Keys: Local Configuration Save
  4. Connect to the reader that is not working and upload (Load) the file saved above.

    MBTB Manage Configuration Keys: Local Configuration Load

The two readers now have identical Morpho configurations and should work the same. Set the second reader to the correct mode. It may also be worth setting the MIFARE keys again from the Command Centre client.