Configure IDEMIA readers over OSDP

Connect IDEMIA (Morpho) readers through OSDP with correct addressing, wiring, and reader overrides.

Command Centre v9.00 adds OSDP for IDEMIA readers. Use v9.00 MR1, which has a more reliable add, a 'Reboot' override, and an improved tamper alarm.

Supported firmware for OSDP

Use the latest firmware version available, from IDEMIA products. The minimum supported firmware is:

  • Sigma family 4.5.0.

  • MorphoWave SP 1.2.7.

  • VisionPass and MorphoWave XP support OSDP by default.

Configure

  1. Drag the reader onto the Controller OSDP RS485 Bus.

  2. Give it a unique address 0–126, then apply. Command Centre configures everything when you drag the reader to the OSDP RS485 Bus window and select Apply.

  3. Check the reader status. Status shows Secure OSDP Communication (encrypted by default).

The OSDP bus baud rate has 4 options. The baud rate must match per bus, so it must be the same for each RS485 bus. Use 115200 for better performance.

For general OSDP addressing, see OSDP - Setting up an OSDP device for the first time.

Wiring

Sigma Lite and Sigma Lite+ readers (RS485 only):

Morpho readers that support RS485 only
Controller RS485 port

RS485_A Blue

A

RS485_B Blue / Red

B

RS485_GND Black / Red

- (Ground)

VisionPass, MorphoWave, Sigma Extreme and Sigma Wide readers (RS422 and RS485):

Morpho readers that support RS422 & RS485
Controller RS485 port

RS485_TX_Z Green / Black + Blue/Black

A

RS485_TX_Y Green / White + Blue/White

B

RS485_GND Black / Red

- (Ground)

TX and RX are abbreviations for Transmit and Receive.

Overrides

  • Shunt / Unshunt stops reader comms and I/O. Shunt stops communication to the reader, and all inputs and outputs on that reader are unavailable to the system until you perform an Unshunt override.

  • Re-initialise Encryption is for a replaced reader reusing an old IP, or a status of "Encryption required". A replacement reader still uses the previous reader's IP address. To correct this, a Re-initialise Encryption override is required. If the status shows "Encryption required" during OSDP assignment, the operator can also use this override.

  • Reboot (v9.00 MR1) reboots the reader.

Reader display messages

LCD readers show zone state (for example 'Secure' or 'Dual authority') and Access granted. Off shows a coloured bar only, for access granted or denied. By default, Reader Display Messages is set to 'Use site default settings'.

A reboot is required to clear the text box.

OSDP troubleshooting

Problem
Possible cause(s)
Solution

OSDP Morpho reader not coming online with status displaying "The device is not responding."

The reader has been replaced.

Perform a "Push Configuration" override.

OSDP Reader not coming online.

Network disconnection, device offline.

Remove the OSDP reader from the OSDP tab of the Controller, then add it back again.

Bad packet alarm generated Invalid packet type: 0x6B

Using a MorphoWave SP reader with old firmware can cause this when "Show reader display messages" is ticked.

Either turn off "Show reader display messages" (the MorphoWave SP does not have an LCD screen), or update the firmware to the latest version.

Copying and pasting an OSDP-connected Morpho reader links the copy to the original. See IDEMIA reader troubleshooting.

Factory default

  1. Power off the terminal.

  2. Remove the terminal from the bracket (wall).

  3. Connect these pins together: GPO_0 (Yellow) to Wiegand_IN0 (Green/Red), and GPI_1 (Orange/Red) to Wiegand_Out1 (White).

  4. Power on the terminal.

The menu and hardware factory-reset procedures, with the firmware condition and default IP, are on IDEMIA reader troubleshooting.