For the complete documentation index, see llms.txt. This page is also available as Markdown.

ThyssenKrupp integration reference

Reference ThyssenKrupp integration versions, licensing, features, network ports, and data flow.

Use this reference to plan a ThyssenKrupp elevator integration and confirm its technical requirements.

Integration versions

Version
Command Centre requirement
Architecture

7.10

7.10 and later

Serial connection from Controller 6000

8.10 through 8.30

8.10 through 8.30

ThyssenKruppEthernet service

8.40 and later

8.40 and later

ThyssenKrupp Insight through the Elevator Service

Command Centre 8.40 and later replaces the earlier Ethernet service. Do not retain the Gallagher ThyssenKrupp Ethernet 8.20.2 package on these deployments.

Licensing

ThyssenKrupp Insight requires the ThyssenKruppInsight license feature.

Supported features

ThyssenKrupp Insight supports kiosk and elevator car terminals, Gallagher-controlled readers, and front and rear elevator-car doors. Controller 6000 makes access decisions.

Command Centre 8.40 supports Extended Time/Assistance for accessibility prompts or extended door-open time. Version 8.50 adds default floors, passenger types, and ThyssenKrupp embedded-reader credentials.

Data flow

Cardholder data remains on Command Centre controllers. The Elevator Service does not send card numbers or personal data to the ThyssenKrupp system.

The Elevator Service receives Card Swipe or RegisterCall messages. It converts them into the ThyssenKrupp format. Command Centre also uses the service for device discovery.

Network ports

Network
Port
Protocol
Purpose

Controller network

8906

TCP

Controllers

Controller network

65000

TCP

Command Centre Service

ThyssenKrupp Elevator System network

8039 through 8041

UDP

ThyssenKrupp communication

For serial interface limits and vendor comparisons, see Elevator integration interfaces and limits.

Last updated

Was this helpful?