For the complete documentation index, see llms.txt. Markdown versions of documentation pages are available by appending .md to page URLs.
Skip to content

Otis Compass HLI connection issues

Diagnose Otis Compass HLI routing, multicast, logging, and floor-selection issues.

Fault finding, log collection, and common alarm types for the Otis Compass HLI integration.

For architecture, licensing, network setup, and reader support, see Otis.

Networking - the most common issue

Most Otis integration issues are network routing problems, especially when controllers are on a different subnet. The FT Otis Compass HLI Service communicates with the Otis Layer 3 switch using the 192.168.50.250 network interface via UDP Multicast.

Network diagram - CC server with two NICs, directly connected to Otis Layer 3 switch, showing the Multicast traffic path

From CC 9.10, Otis recommends switching from Multicast to Unicast to avoid multicast routing issues.

Check the routing table - first step

This is the first thing to check when an Otis system is not coming online.

Open a command prompt on the CC server and run:

Verify the multicast route entry 224.0.0.0 exists and points to 192.168.50.250:

Routing table - working configuration showing 224.0.0.0 240.0.0.0 192.168.50.250 192.168.50.250 with metric 55

The highlighted entry should show: 224.0.0.0 240.0.0.0 192.168.50.250 192.168.50.250 55 (the metric value may differ, but the interface must be 192.168.50.250).

If the entry is wrong or missing:

Routing table - broken configuration showing the wrong interface assigned to the multicast route

Delete and recreate the route:

Where X = the interface number of the 192.168.50.250 NIC. Find it via ipconfig /all, matching the MAC address to the interface number shown in route print.

This issue is commonly caused by a Channel Partner adding a new NIC and not restoring the routing table correctly.

Check network card priority

Occasionally (reportedly after Windows updates), network card metric priorities are reversed. The 192.168.50.250 NIC's metric must be lower than the Controller/Internet NIC's metric.

Example: if the controller network NIC had metric 25 (lower than the Otis NIC at 35), increase the controller NIC's metric above 35, for example set it to 50.

Network card metric configuration - showing the correct metric values using netsh, with the Otis NIC metric lower than the controller network NIC

Symptom of incorrect priority: all DECs fail to come online. The event viewer shows:

Enabling logging

Log the Otis Compass HLI Service

Edit OtisCompassHliService.exe.config and uncomment the Debug line:

Before:

After:

The log file is created at: Log\OtisCompassHliService.log

Registry keys for logging

Registry location: Computer\HKEY_LOCAL_MACHINE\SOFTWARE\Gallagher\Command Centre

Create DWORD keys as needed:

Key
Value
Purpose

LogControllerComm

1

Log Controller to FT Otis Compass HLI Service communication (requires Debug enabled)

LogUdpMulticast

Non-zero

Log UDP Multicast packets (requires Debug enabled)

LogUdpUnicast

Non-zero

Log UDP Unicast packets (requires Debug enabled)

Controller-level logging

Add to the Additional Configuration field on the Advanced tab of the Elevator HLI:

Parameter
Purpose

log_raw_data=1

Logs outgoing and incoming packets in hexadecimal format

raise_debug_event=n

Raises additional debugging alarms (n = debugging level)

Note: these parameters impact controller performance and will slow normal operation on busy sites. Controller logs are overwritten when the log reaches 1 MB. On busy sites this can be 10 minutes or less. Remove after fault-finding.

Wireshark

Otis engineers indicate that port 23 on their switch is configured as a mirror port. Plug a laptop into that port to capture all traffic with Wireshark.

Common alarms

"Card Did Not Select a Level"

CC event showing "card did not select a level" alarm

Cause: the cardholder is attempting to badge to the floor they are currently on.

Example: cardholder is on floor 6 and badges to go to floor 6 again. No movement is needed, so the system logs "did not select a level".

"Floor Out of Bounds"

CC event showing "floor out of bounds" alarm

Cause: the floor being requested exceeds the configured floor count.

Example: the system is configured for 5 floors but the 6th floor is being selected.

Resolution: check the floor_offset setting is correct. If there are 2 basement levels, the offset is typically -2. Confirm the correct offset with the Otis Technician, do not assume.


🔗 Related

  • Otis. Architecture, licensing, and network setup.

Last updated

Was this helpful?