Elevator integration interfaces and limits
Compare elevator interface types, controller limits, port use, and performance guidance.
Gallagher integrates with four major elevator brands via three distinct interface methods. The interface type drives the wiring, software configuration, and item type used in Command Centre.
Supported brands: Kone, Otis, Schindler, ThyssenKrupp.
Two elevator system types
Conventional dispatching
Any available lift serves any request. Passengers select their own floor inside the car.
Destination-based dispatching
The system groups passengers by destination floor before they enter and assigns a specific car.


Conventional: all passengers compete for the same available lift. Other cars sit idle.


Destination-based: the system pre-assigns lifts by floor group before passengers board.
Three interface types
RS232 - Wired Serial Cable
Used by: Kone (standard), Otis, Otis Modbus, Schindler, ThyssenKrupp v7.10+.
A physical serial cable connects the C6000's RS232 port directly to the elevator system panel.

Requirements:
RS232 cable wired to the controller hardware port.
Elevator HLI item configured in Command Centre under Controller > Serial Devices tab.

TCP/IP - Network Connection
Used by: Kone ELI, Otis Compass, Schindler system variants.
No physical serial cable. Communication goes over LAN. The controller's Serial Device software slot is still used, but the RS232 hardware port is not.

Note: Even without a cable, the controller's Serial Device slot is consumed and unavailable for other purposes. The Elevator HLI item is still required for some variants.
Schindler note: Requires a middleware machine, which is unique among all integrations.

Gallagher Elevator Service - TCP/IP with Service Layer
Used by: Kone Office Flow, ThyssenKrupp v8.10-8.30, ThyssenKrupp Insight (v8.40+).
A separate Windows service (GGL Elevator Service) sits between the Gallagher server and the elevator system. This is the most modern integration path.

Key difference: Uses the Elevator System item type in Command Centre, not Elevator HLI. There is no dependency on the controller's Serial Device slot or RS232 port.
HLI comparison table

RS232 Port column values:
use
Physical serial cable required and connected to the controller port
consume
No cable needed but the port is locked and cannot be used for other purposes
unused
Port remains free for other purposes
For the full compatibility matrix including CC version requirements, refer to the CC Compatibility Matrix.
System limits (C6000)
Levels per elevator car
256
-
Elevator cars per controller
8
Max configuration size per C6000
Transactions per second
2
Across all access items (doors and lifts) on that controller
In practice the binding limits are 20 HBUS readers per controller and 2 events per second per controller.
Performance guidelines
Place the Elevator Car HLI item and its reader on the same controller.
Use one access group covering all required levels rather than multiple single-level groups. This reduces transaction overhead significantly.
Use the "Change to Disarmed state" Alarm Zone privilege sparingly, as it significantly impacts response time. If used, keep the Alarm Zone on the same controller as the elevator car.