Bad Input - Parts reporting Bad Input
Command Centre - Errors › Bad Input - Parts reporting Bad Input
An alarm is raised with the controller reporting bad input messages. This is difficult to reproduce and the circumstances can vary.

Logs needed
Command Centre logs
Controller logs
The Controller's Application logs
Note: GeneralOn should be enabled along with Trace.
Log format to capture
Field breakdown:
Receiving side, the item receiving bad input from the source: Part number, Input number.
Source, the item generating the bad input: Bert# (controller number), Part number, Output number, Alarm priority.
Find the faulty item
Web-browse to the controller and navigate to the Parts Manager and Secondary Parts Manager. Note the Bert#, which identifies which Controller 7000 it is, for example Controller #2.

Locate the Source Part number from the list, for example Part 87, a Relay Part.

Click the Part for its properties. Note the Point ID; this is equivalent to the FTItemID in Command Centre.

Use the Find Tool with two left square brackets
[[followed by the FTItemID to locate the item in the Configuration Client.

Workaround
Confirm the controller where the item is configured has the correct software version assigned.

Push the configuration on the controller.
If the issue still occurs, de-configure the item and create a new item to replace it.
Worst case, DIP2 the controller to lose its configuration.
Optional: also de-configure the receiving item
For example Part 104, another Relay Part.




Last updated
Was this helpful?