Error while connecting to specified server: Method '' of object

Command Centre - Connection Issues › Method '' of object '' failed

Error: "Method '' of object '' failed" from the OPC Bridge Configuration tool.

Cause: the OPC username and password registry keys are missing.

Resolution

  1. Open Registry Editor (you may need Administrator privileges).

  2. Locate:

    • (32-bit OS): HKEY_LOCAL_MACHINE\SOFTWARE\Gallagher\Command Centre

    • (64-bit OS): HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Gallagher\Command Centre

  3. Right-click in the empty space and select String Value (REG_SZ). Create two keys named:

    • OPCUserName

    • OPCPassword

  4. Enter an OPC username and password in the Value Data.

⚠️ Security: Create a separate OPC operator account with only the required privileges. The username and password stored in these registry keys are not encrypted.

Then try to connect to the OPC Server in the OPC Bridge Configuration tool again.

Method of object failed, registry keys
OPC registry string values