Error while connecting to specified server: Method '' of object
Command Centre - Connection Issues › Method '' of object '' failed
Error: "Method '' of object '' failed" from the OPC Bridge Configuration tool.
Cause: the OPC username and password registry keys are missing.
Resolution
Open Registry Editor (you may need Administrator privileges).
Locate:
(32-bit OS):
HKEY_LOCAL_MACHINE\SOFTWARE\Gallagher\Command Centre(64-bit OS):
HKEY_LOCAL_MACHINE\SOFTWARE\Wow6432Node\Gallagher\Command Centre
Right-click in the empty space and select String Value (REG_SZ). Create two keys named:
OPCUserNameOPCPassword
Enter an OPC username and password in the Value Data.
⚠️ Security: Create a separate OPC operator account with only the required privileges. The username and password stored in these registry keys are not encrypted.
Then try to connect to the OPC Server in the OPC Bridge Configuration tool again.


🔗 Related
OPC Connections 7.90 and higher - DCOM changes. The DCOM transport change that affects OPC.
Last updated
Was this helpful?