OSDP - setting up an OSDP device for the first time

Assign unique addresses when connecting OSDP devices to Controller 6000.

About OSDP

OSDP (Open Supervised Device Protocol) is an access-control communications standard from the Security Industry Association (SIA). It is the modern replacement for the roughly 40-year-old Wiegand protocol. Wiegand is unencrypted (and so hackable), unsupervised, uni-directional, and cannot be daisy-chained, because each reader home-runs to the controller over a limited distance. OSDP is a non-proprietary, bi-directional RS485 interface that lets readers, controllers, and I/O boards talk to each other.

⚠️ OSDP, like all RS485 protocols, does NOT support Star-connected wiring. Always run OSDP in Daisy Chain configuration.

Gallagher support:

  • OSDP v2.1.6, available from Command Centre v7.30.

  • OSDP connectivity on each of the two RS-485 ports of the Controller 6000 only. Up to 16 OSDP readers per controller across a maximum of 10 controlled doors (8 OSDP readers per RS485 port).

  • Supports OSDP-enabled card and card + PIN readers.

Setting up a new device

A new OSDP device usually ships with address 0 or 1, which conflicts if you put more than one on a controller's OSDP bus.

  1. Connect only one OSDP device at a time to the controller.

  2. Assign it a new, non-conflicting ID (note the identity for future replacement).

  3. With the reader online, select the new address and apply it. The device's OSDP address updates.

  4. Connect the next device and re-address it. Repeat until all are connected.

Command Centre OSDP device pairing: the Change Device Address section (device list, Configured and Device Address, Change Address) and OSDP Bus Baudrate 115200

OSDP-connected readers also feature in specific reader integrations. For example, IDEMIA (Morpho) and Invixium readers both support OSDP.