BACnet - basic setup requirements
Prepare Controller 6000 and BACnet devices for a BACnet integration.
About BACnet
Gallagher's BACnet Protocol Interface gives Command Centre bi-directional communication with BACnet-compatible devices. Specified Controller 6000s act as BACnet clients to read and write BACnet Object values.
Inbound: monitor BACnet objects for state changes and raise alarms.
Outbound: change BACnet object state in response to events.
This makes Command Centre the central repository for all site alarms (boiler, chiller, and aircon failures, and maintenance alarms) with full event and alarm management. It also supports access-driven environment control for energy savings, such as lighting and aircon that come on with a valid badge and shut down when there is no movement.
BACnet is supported on Command Centre v8.10 through v9.40 (every version).
Basic setup requirements
Third-party BACnet systems need hardware so the Gallagher controller can monitor and command them. Command Centre hardware (IO, readers, doors) cannot be monitored by other BACnet systems.
The Controller using the BACnet customisation must be on the same subnet as the BACnet devices.
The Controller's BACnet Device ID is derived from its MAC address. The message "The BACnet Device ID is already in use by another Controller" means it is not unique.
The Controller 6000 broadcasts the BACnet Device ID (configured on the Setup tab of the BACnet Device in External Systems). The third-party BACnet should respond with its IP. If it does not, the device will not come online, which is usually a network issue.
Web-browsing the controller shows received IPs. For example, Address Count 3/255 means 3 configured BACnet devices have broadcast the ID and received an IP. 255 is the maximum configurable.