Configure a turnstile with one door and two outputs
Use one door license and Logic Blocks to control two turnstile outputs.
This pattern lets one door licence drive two outputs for a turnstile or flap barrier that needs two triggering outputs (for example, separate dry-contact relays for a "Welcome" or "Goodbye" audio response). The trick is to combine the door's unlock output with the reader's Card Read Output through a logic block, so the second output only fires on a valid access, not on any card read.
Use case
This allows the administrator to use only one door licence while providing two outputs for a turnstile or flap barrier that requires two triggering outputs (such as a dry contact or relay for a "Welcome" or "Goodbye" audio response).
Entry reader configuration requirements
A. 2 virtual outputs
Item 1: Door unlock output. A virtual output the door is configured to use as a "valid granted access".
Item 2: Card Reader's Output control. Reflects which reader is used on the turnstile (entry or exit) and is used as a "signal".
B. 1 logic block
Secures the decision made from valid access granted.
C. 2 outputs (item A)
1 item serves as the Entry Unlock Output (Input 1, entry for the turnstile).
1 item serves as the Exit Unlock Output (Input 2, exit for the turnstile).
Configuration logic
The virtual output assigned to the Card Read Output triggers whenever a card (any card, valid or not) is read from the reader. It signals which side of the turnstile a cardholder goes through, so the system can identify whether the badge is from the entry or exit side.
The logic block is configured so that only valid access triggers its reflected output, which the turnstile then uses as input 1 (respectively input 2).
On a valid cardholder access: the door's Unlock Output (item 1) triggers along with the entry reader's Card Read Output (item 2). This satisfies the logic block's rules and triggers the Output configured on its Reflected Output (item A).
On an invalid cardholder access: the door's Unlock Output (item 1) does NOT trigger while the entry reader's Card Read Output (item 2) does. Since the logic block's rules are not met, the unlock output does not trigger and therefore does NOT trigger the turnstile.

Note: By design, the Card Read Output will trigger any output or relay configured in it the moment a card is read from the reader, regardless of whether the card is valid or not.
Exit reader configuration
Configuration for the exit reader follows the same logic as the entry reader.

Related links
Scenario - Pulsing an output using Logic Blocks. The general logic-block mechanism used here.
Command Centre - Access Groups. Granting the access that a valid turnstile passage depends on.
Last updated