Redundancy and failover
Plan Command Centre failover while ensuring only one service instance uses SQL.
Failover is the automatic transition to a standby server when the primary fails.
Switchover is the same thing done manually. Controllers and doors keep operating and recording events independently when the Command Centre server is unavailable. Gallagher provides a Stratus redundancy solution and supports two DNS-based arrangements. The hard rule across every arrangement: only one Command Centre service instance may talk to the SQL instance at a time.
Failover vs switchover
Failover is the automatic transition to a redundant or standby server, system, hardware component, or network when the primary fails or terminates unexpectedly.
Switchover performs the same function, but it is a manual process that requires human intervention and typically happens with prior notice.
Some sites implement third-party failover or redundancy solutions for their Command Centre servers. Gallagher does not provide support for configuring third-party failover software, but can assist with the setup and configuration of the Command Centre software itself.
Stratus (Penguin Solutions)
Gallagher provides Stratus redundancy solutions for Command Centre servers. The Stratus product line is owned by Penguin Solutions. For the specific fault-tolerant options (ftServer lockstep hardware, everRun and everRun SplitSite software fault-tolerance, and ztC Edge edge appliance), including part numbers and the ztC Edge support ceiling, see Penguin Solutions Technologies (Stratus).
Other failover arrangements
Single SQL server with DNS redirection
This arrangement uses:
A single SQL server holding the Command Centre databases.
Two servers with Command Centre services installed, both connected to that SQL database.
Only one of the two Command Centre servers may have its services running at a time.
DNS servers direct controller and workstation traffic to whichever Command Centre services are running.
How it behaves:
There must be a mechanism to update the DNS server's records to point network traffic at the active Command Centre services. This is the site's responsibility to arrange. Command Centre does not have this feature.
At no stage may more than one instance of Command Centre services communicate with the SQL instance.
Controllers take a few minutes to update themselves from the DNS server, then come back online after a transfer between servers.
Dual mirrored standalone servers
Essentially the same outcome as Stratus/everRun, but with considerably more setup and ongoing maintenance effort:
Two servers run side by side. One has its Command Centre services disabled.
The SQL databases are mirrored between the two servers.
At no stage should both servers have the Command Centre services running.
A DNS server is needed to control network traffic to the active server.
As above, there must be a site-provided mechanism to update the DNS records to point traffic at the active Command Centre services. Command Centre does not provide this.
The invariant
Across every arrangement above, the single rule that must never be broken: only one Command Centre service instance may be connected to and running against the SQL instance at any time. Two live instances against one database is an unsupported and damaging state.
🔗 Related
Penguin Solutions Technologies (Stratus). The supported fault-tolerant hardware and software options.
Controllers. Why controllers keep operating when the server is down.
Last updated