Fatigue management vs regulated zones

Fatigue Management and Regulated Zones are the same customisation under two names. They manage how long a cardholder may spend on site or in parts of the site.

Fatigue Management was the original name (introduced v7.10). It was renamed to Regulated Zones in v7.30. New work uses Regulated Zones. The only practical difference between the two is the name and the licensing string.

The rename

Fatigue Management was introduced in v7.10, then renamed in v7.30 to Regulated Zones. Both do the same thing: manage cardholder time on site, or in parts of the site.

Fatigue Management
Regulated Zones

Available version

v7.10 to v7.20

v7.10 or later

Licensing string

[Limits] Fatigue Zones=1 [Customisations] FatigueManagement=1

[Limits] Regulated Zones=1 [Customisations] RegulatedZones=1

If a site's licence still carries the FatigueManagement=1 customisation string, it predates the v7.30 rename. The current string is RegulatedZones=1. The capability is the same; only the name and licence string changed.

How it works: monitoring mechanics

A Regulated Zone item is separate from, but potentially encompasses, one or more Access Zones. It works with core Command Centre alarm monitoring and control to help ensure the health and safety of employees or contractors on site, managing cardholder time on site. Supported in v8.10 to v9.40 (every version).

Monitoring parameters

  • Cumulative Duration: accumulated time on site across multiple shifts. An event raises when a cardholder exceeds the configured cumulative shift duration within a specified period.

  • Break Duration: minimum break period between shifts. An event raises if a cardholder re-enters within the minimum break period. A configurable temporary exit grace period defines how long a cardholder may be off-site before being considered "between shifts."

  • Maximum Duration: time on site within a single shift. An event raises if exceeded.

  • Predictive Cumulative Duration: predicts whether a cardholder, if they stayed for their expected shift duration, would end up at or above the cumulative limit, raising a predictive alarm if so.

Reporting and notification tools

An Activity Report on fatigue events (all or specific cardholders, over a period); a Notifications Filter to notify cardholders when a fatigue event occurs (Notifications is a separately licensed feature); a Site Configuration Report (Command Centre Classic) on a Regulated Zone FT Item's configuration.

Shift management (added v8.30, enhanced v9.20)

Monitors and optionally enforces cardholder compliance with shift patterns, with configurable early/late arrival and late-departure grace periods:

Configuration method
Grace periods
Alarms raised for

PDF Shifts

0, 1, 2, or 3 days

Early arrival, Late departure

'Shifts' feature (v9.20+ only)

Between 0h00m and 23h59m

Early arrival, Late arrival, Late departure

If a Competency is used, it is disabled or enabled in line with the shift. Instead of an early-arrival alarm, the cardholder is denied access until the Competency auto-enables at the start of their shift (start of the Start-shift grace period). Shift patterns are a start date, an optional end date, and a pattern (for example 7 days on / 7 off) defining access-granted vs access-disabled days.

Example (PDF Shifts): a 7-on/7-off pattern with a 1-day grace period can be configured to alarm if a cardholder arrives more than 1 day early, or has not left after 8 days (7 + grace) since shift start.

Maximum entries (added v8.75)

Monitors and restricts how many times a cardholder may enter an area within a specified period. An alarm raises if exceeded.

Use cases

  • Mining (original): a mining-industry customer needing to manage staff fatigue under regulation, governing time-on-site per shift, across shifts, and minimum inter-shift breaks.

  • Prison: alert a guard if visitors overstay a defined area.

  • Hospital: alert staff if day-leave patients do not return on time.