Monitoring

Configure, test, and troubleshoot alarm transmission to a monitoring station.

For an input to generate a Contact ID event that reaches a monitoring station, all of the following must be in place:

  1. A Controller

  2. A Dialler (IP or Analog) with a monitoring station configured and an Account

  3. An Alarm Zone connected to the controller, with a Group Identifier (GG) configured. Selecting the Alarm Transmitter under the alarm zone's Connections makes it send Arm/Disarm messages to the monitoring station.

  4. An Input with a Zone identifier (CCC) configured

  5. An Action Plan that triggers an event of Very Low Priority or higher and has the dialler selected

Minimum monitoring config showing the dialler and monitoring account
Alarm zone with a Group Identifier configured
Input with a zone identifier configured
Action plan with the dialler selected

Place the action plan

The action plan can be assigned at three locations, each with a trade-off:

Location
Pro
Con

Server Properties

Single set up

Entire system behaves the same

Alarm Zone

Quicker to set up

Everything on the alarm zone behaves the same

Device (the input)

Precise control of each item's behaviour

Takes a lot of time to configure

You can mix and match. There is a priority order when more than one applies:

  1. Highest priority: configuration on the Device (the input, in this example)

  2. Middle priority: configuration on the Alarm Zone

  3. Lowest priority: configuration at Server Properties

So a setting on the alarm zone is overridden by whatever is set at the device.


Verify the configuration

Two ways to test:

  • Live test: activate the alarm and confirm receipt with the monitoring station.

  • Report test: in the Configuration Client / Report, create a Contact ID report. A correctly configured input and zone produce output similar to:

If an alarm zone or device is not listed in the report, it is not configured to send events.


Duress inputs

Configuring a device (typically an input) with a Contact ID code of 121 or 126 results in no message being transmitted to monitoring. These codes are linked to a user, not a zone (usually assigned to a door), so they do not produce a zone event.

For monitored duress signalling, use Contact ID code 120 (Panic) instead. See Alarm Transmission - Ademco Format for the full code list.