IP dialler

Configure IP dialler network access, ports, and DC-09 or CSV monitoring protocols.

The IP Alarm Transmitter is part of the firmware on the 6000/7000 controller and simply needs to be configured.

  • Only one IP dialler per 6000/7000 controller.

  • The controller with the IP dialler must be able to reach the Internet to establish a connection with the remote monitoring station. IT staff must open a communication path through the site's router.

  • The default port is 29000, but this can be changed in the IP dialler configuration.

IP dialler configuration

Two protocols are available for the alarm dialler:

Protocol
Available from
Requirement
Notes

DC-09

v6.10

Gallagher Monitoring software installed at the monitoring station

Each event message transmission is approximately 900 bytes (with or without encryption)

CSV

v7.20 as a customisation; core from v7.30

Monitoring station has CSV capability

Allows Command Centre to connect directly to an external monitoring centre, no Gallagher software required at the station