For the complete documentation index, see llms.txt. Markdown versions of documentation pages are available by appending .md to page URLs.
Skip to content

IP monitoring

Understand DC-09 and CSV alarm monitoring connections for Gallagher and third-party receivers.

DC-09 with Gallagher IP Receiver software

The flow when the monitoring centre runs the Gallagher IP Alarm Receiver:

  1. An alarm is generated on an alarm zone on any controller (for example, Controller 3).

  2. The message is sent to the controller hosting the IP transmitter (for example, Controller 1).

  3. That controller uses its gateway information to route the traffic out through the site's router/firewall to the monitoring station's IP address.

  4. The Gallagher IP Alarm Receiver at the monitoring centre decodes the message (and decrypts it if encryption is enabled), then sends it via RS232 to the monitoring server.

DC-09 connection with the Gallagher IP receiver
Relationship between Command Centre components and the DC-09 packet

DC-09 without Gallagher IP Receiver software (direct to a third party)

⚠️ Supported only from v8.70.2078 (MR3), v8.80.1025 (MR1) and v8.90+.

To connect the DC-09 protocol directly to a monitoring facility that has IP DC-09 receiving capability:

  1. In Configuration Client under File / Server Properties and/or the Alarm Zone, go to Alarm Transmission and add an Account Prefix other than 0s.

    • The monitoring station should supply the Account Prefix number. (The Account Prefix is an extension to the monitoring facility's account code.)

    • If they do not supply one, populate the field with 001 and advise the monitoring station of the value you applied. Any HEX ASCII characters other than 0 will work, but the monitoring station must know what it is.

Account prefix field
  1. On the IP Transmitter(s) under Alarm Receivers, the Transmitter ID can be set to anything. Adding the Account Prefix overrides this setting.

IP transmitter alarm receivers
  1. Under the Protocol tab, Encryption must be blank / unchecked.

Protocol tab with encryption unchecked

This allows an IP Transmitter to connect to a third-party alarm receiver.

Relationship between Command Centre components and the direct DC-09 packet

Note: Prefix = Line Card in DC-09. Many USA alarm monitoring companies call this DNIS.

Note: Encryption for this direct configuration is planned to be released in the future.

Note: After setting the prefix to a value other than 0, the Gallagher IP Receiver software can still be used, but not configured as before. The ACCT is sent in place of the Transmitter ID, so the software must be reconfigured to accept the ACCT value in the Transmitter ID field. A 4-character ACCT is prepended with two zeros, so an ACCT of 1235 would be entered as 001235 in the Gallagher IP Alarm Receiver configuration.


CSV connection

The CSV protocol does not require the monitoring station to have the Gallagher IP Monitoring software installed. The monitoring station needs to be able to accept CSV connections, which is often an add-on to the monitoring suite they use.

CSV connection architecture

Last updated

Was this helpful?