Permaconn diallers

Connect and configure Permaconn diallers with Gallagher controllers.

A Permaconn dialler connects directly to the serial port of a controller and acts as an analog dialler. Configure it as a standard dialler and add the atX0 command (as in the Analog Dialler section), then wire it per the diagram.

Configuration of the Permaconn dialler itself is up to the Channel Partner / monitoring facility.

Permaconn to Gallagher panel wiring

Verify with Permaconn that the serial wiring is correct. There are many Permaconn dialler models, and wiring differs between them.


Permaconn PM1048 v3 (3G/4G) and PM54

These models provide serial data communication via RS232 between the Gallagher panel's RX and TX terminals.

  • Set up Gallagher dialler commands as normal in Command Centre. The PM1048 and PM54 emulate the Gallagher dialler.

  • Enable Periodic Dial Tone and set it to check every one minute.

  • Set Redial Attempts to the maximum of 99 times.

The PM1048 and PM54 should come with their own RS232 connection cable.

Periodic dial tone setting
Redial attempts set to 99

Permaconn PM 45 4G

The PM 45 4G requires a firmware update and the RX and TX connections reversed on the Permaconn before the unit communicates correctly.

If the dialler does not respond as expected in the Status and Overrides dialog, investigate:

  1. The wiring connecting the 6000 and the Permaconn unit is not correct.

  2. Contact the Technical Support site for the facility that supplied the Permaconn unit.