Analog dialler

Connect and configure analog diallers, cellular diallers, PABX prefixes, and jumper settings.

The Analog Dialler uses an RS232 (serial) port to connect to a PSTN dialler that sends Ademco Contact ID over a phone line. There are two hardware versions:

Part
Firmware compatibility

C200621

Controllers running v8.10 firmware or earlier

C200620

Controllers running v8.20 firmware or later

If a site upgrades from v8.10 or earlier to v8.20 or higher, the C200621 will continue to work on the later versions of Command Centre.


C200620 connection

The C200620 connects to the RS232 serial port of a 3000 or 6000 controller and to an analog telephone / POTS (Plain Old Telephone Service) line.

  • Connect the building incoming telephone line to the P3 "Line in" connector.

  • Connect all other devices to the P2 "Line out" connector.

This way, when the dialler activates it disconnects the other devices and is the only device left on the line. This is intended: you do not want other devices on the phone line interfering with the alarm system reaching the monitoring station. The dialler uses a relay to disconnect the output from the phone line.

C200620 analog dialler connection
Analog dialler connection detail

This device, like all analog diallers, has been known to have issues connecting to digital telephone lines and some PABXs.


Connect a cellular dialler

A cellular unit is usually supplied by the monitoring centre, often pre-configured with an account code (but not always). Cellular units vary, so getting one working may take trial and error.

  • Some do not have phone-line dial-tone emulation.

  • Some cellular backup devices require the Analog Dialler to be connected.


Configure phone lines with no dial tone

If the dialler must connect and dial without waiting for a dial tone, add a Custom Initialisation String of atX0 or atX1 in the dialler's Dial Protocol tab.


Configure a PABX prefix number

In some countries this is referred to as the DNIS number. It is the entry you put into the Analog Dialler to get through a PABX to an outside line.

PABX prefix / DNIS field

"No response from modem"

If you get a "No response from modem" message, especially after installing a new analog dialler, the plugin sub-board jumper is the usual cause. There are two versions of the sub-board, set at assembly but occasionally missed.

Check P7 on the dialler main board:

Sub-board part number
P7 jumper position

MT5692SMI-X-L-92.R1 or SM H2

3V3

MT5692SMI-92.R1

5V

P7 jumper on 3V3
MT5692SMI-X-L-92.R1 sub-board
MT5692SMI-92.R1 sub-board (5V variant)
SM H2 sub-board

Check P6 on the dialler main board: the main board has an option for a P6 jumper. If a jumper is present, remove it. P6 is only used during the manufacturing process and should not be present in the field.

P6 jumper location