Ademco format

Reference Ademco Contact ID fields, DC-09 packet structure, and event codes.

Command Centre transmits alarm events in the Ademco Contact ID format over both Analog (PSTN dialler) and IP (DC-09) transports. This page is the format reference. For how to set up monitoring and diallers, see Alarm Transmission - Monitoring.


Alarm Dialler format (PSTN)

The Alarm Dialler (Dialer in the USA) is a component that uses an RS232 (serial) port to connect to a PSTN dialler and send messages using ADEMCO Contact ID, an industry standard across the world since 1999.

The format of the message is:

ACCT  MT  Q XYZ  GG  CCC
Field
Meaning

ACCT

4-digit account number (0-9, B-F). Set in either the System Properties or in the Alarm Zone itself.

MT

Message Type. A 2-digit sequence identifying the Contact ID message to the receiver. Transmitted as either 18 (preferred) or 98 (optional). New receiver implementations accept either; some older receivers may not accept 98.

Q

Event qualifier: 1 = New Event or Opening; 3 = New Restore or Closing; 6 = Previously reported condition still present (status report).

XYZ

Event code (3 hex digits, 0-9, B-F). Decided by the event type selected at the Input Properties. See the addendum table below.

GG

Group or Partition number (2 hex digits, 0-9, B-F). This is the Alarm Zone in Command Centre. Use 00 to indicate no specific group or partition applies.

CCC

Zone number (event reports) or User # (open/close reports), 3 hex digits (0-9, B-F). Use 000 to indicate no specific zone or user applies.


IP Alarm Transmitter format (DC-09 packet)

The IP Alarm Transmitter sends messages directly from the controller to a monitoring station over TCP/IP instead of a phone line. It has two protocol options, CSV and DC-09. The following explains how the DC-09 message is composed and how it relates to ADEMCO Contact ID.

A controller's outgoing message, observable in the controller's debug webpage under Parts Manager > Alarm Transmitter Part, may look like:

"ADM-CID"0005L98765#001235[#001235|1423 44 777]_17:15:19,03-06-2026
"ADM-CID"0006L98765#001235[#001235|3423 44 777]_17:15:30,03-06-2026

The format is:

The second half (between | and ], which DC-09 calls the DATA) is almost identical to the Alarm Dialler format, except there is no MT. The ACCT is sent as 6 digits, so an ACCT of 1235 in Command Centre is padded to 001235.

Aside from time and date, there are four new components: ID, SEQ, LLLLL, RI:

Field
Meaning

ID

The format, always "ADM-CID" within Command Centre. Tells the receiver we are using ADEMCO Contact ID format in the DATA.

SEQ

The sequence of messages (for example 0005, then 0006 on the next message).

LLLLL

Line Card. In Command Centre this is called the Prefix. For American monitoring stations this is typically known as DNIS, despite that being an antiquated term.

RI

Receiver ID. The field that causes the most confusion.

Receiver ID behaviour changed by version

RI is intended to be an ID for the device sending the message (a panel ID, or a Transmitter ID as Command Centre calls it). However, Command Centre versions v8.70.2078+ (MR3+), v8.80.1025+ (MR1+) and v8.90+ behave differently since the Prefix field was added:

  • If Prefix is set to 0 then the old behaviour remains: the Transmitter ID is sent in this field.

  • If Prefix is populated with something other than 0 then the 6-digit ACCT is sent (as in the two examples above).

How it looks in the Configuration Client:

ADEMCO format configuration in the Configuration Client

Note: The Gallagher IP Alarm Receiver software is still able to receive messages, as long as the 6-digit value of ACCT is configured in the field the receiver software calls Transmitter ID.


Addendum: XYZ event code list

The following is the internationally accepted Contact ID event code list. Note that this is the standard list, not necessarily the event Command Centre will transmit.

XYZ
Name
Type
Description

100

Medical

Zone

A non-specific medical condition exists

101

Personal Emergency

Zone

Emergency Assistance request

102

Fail to report in

Zone

A user has failed to activate a monitoring device

110

Fire

Zone

A non-specific fire alarm condition exists

111

Smoke

Zone

An alarm has been triggered by a smoke detector

112

Combustion

Zone

An alarm has been triggered by a combustion detector

113

Water Flow

Zone

An alarm has been triggered by a water flow detector

114

Heat

Zone

An alarm has been triggered by a heat detector

115

Pull Station

Zone

A pull station has been activated

116

Duct

Zone

An alarm has been triggered by a duct detector

117

Flame

Zone

An alarm has been triggered by a flame detector

118

Near Alarm

Zone

A near-alarm condition has been detected on a fire sensor

120

Panic

Zone

A non-specific hold-up alarm exists

121

Duress

User

A duress code has been entered by a user

122

Silent

Zone

silent hold-up alarm exists

123

Audible

Zone

An audible hold-up alarm exists

124

Duress - Access granted

Zone

A duress code has been entered and granted at an entry door

125

Duress - Egress granted

Zone

A duress code has been entered and granted at an exit door

126

Hold-up suspicion print

User

A user has activated a trigger to indicate a suspicious condition

129

Panic Verifier

Zone

A confirmed Hold-up condition exists

130

Burglary

Zone

A burglary zone has been violated while armed

131

Perimeter

Zone

A perimeter zone has been violated while armed

132

Interior

Zone

An interior zone has been violated while armed

133

24 Hour (Safe)

Zone

A 24 hour burglary zone has been violated

134

Entry/Exit

Zone

An Entry/Exit zone has been violated while armed

135

Day/Night

Zone

An trouble by Day / alarm by Night zone has been violated while armed

136

Outdoor

Zone

An outdoor burglary zone has been violated while armed

137

Tamper

Zone

A burglary zone has been tampered with while armed

138

Near alarm

Zone

A burg sensor has detected a condition which will cause it to go into alarm if the condition worsens

139

Intrusion Verifier

Zone

The specified zone has verified that an intrusion has occurred

140

General Alarm

Zone

The specified zone is in an alarm condition

141

Polling loop open

Zone

An open circuit condition has been detected on a polling loop while the system was armed

142

Polling loop short

Zone

A short circuit condition has been detected on a polling loop while the system was armed

143

Expansion module failure

Zone

A general failure condition has been detected on an expansion module while the system was armed

144

Sensor tamper

Zone

A sensor's tamper has been violated (case opened)

145

Expansion module tamper

Zone

An expansion module's tamper has been violated (cabinet opened)

146

Silent Burglary

Zone

A burglary zone has been violated while armed with no audible notification produced

147

Sensor Supervision Failure

Zone

A sensor's supervisory circuit has reported a failure while the system was armed

150

24 Hour Non-Burglary

Zone

A non-burglary zone has been faulted

151

Gas detected

Zone

The gas detector assigned to the specified zone has reported a fault condition

152

Refrigeration

Zone

The refrigeration detector assigned to the specified zone has reported a fault condition

153

Loss of heat

Zone

The temperature detector assigned to the specified zone has reported a fault condition

154

Water Leakage

Zone

The water leak detector assigned to the specified zone has reported a fault condition

155

Foil Break

Zone

The specified zone which is assigned to foil used as glass break detection has reported a fault condition

156

Day Trouble

Zone

The specified zone which monitors trouble by day has reported a fault condition while disarmed

157

Low bottled gas level

Zone

The gas level detector assigned to the specified zone has reported a fault condition

158

High temp

Zone

The over-temperature detector assigned to the specified zone has reported a fault condition

159

Low temp

Zone

The under-temperature detector assigned to the specified zone has reported a fault condition

161

Loss of air flow

Zone

The air flow detector assigned to the specified zone has reported a fault condition

162

Carbon Monoxide detected

Zone

The carbon monoxide detector assigned to the specified zone has reported a fault condition

163

Tank level

Zone

The tank level detector assigned to the specified zone has reported a fault condition

168

High Humidity

Zone

A High Humidity condition has been detected

169

Low Humidity

Zone

A Low Humidity condition has been detected

200

Fire Supervisory

Zone

The supervisory circuit of the specified fire zone has reported a fault condition

201

Low water pressure

Zone

The water pressure sensor assigned to the specified zone has reported a fault condition

202

Low CO2

Zone

The CO2 pressure sensor assigned to the specified zone has reported a fault condition

203

Gate valve sensor

Zone

The gate valve sensor in the fire sprinkler system assigned to the specified zone has reported a fault condition

204

Low water level

Zone

The water level sensor assigned to the specified zone has reported a fault condition

205

Pump activated

Zone

The pump activity detector assigned to the specified zone has reported an active condition

206

Pump failure

Zone

A pump output monitor assigned to the specified zone has reported a fault condition

300

System Trouble

Zone

A general system trouble condition has been reported by the specified zone

301

AC Loss

Zone

AC power loss has been detected at a control or expansion module while the system was disarmed

302

Low system battery

Zone

A battery has failed a load test while the system was disarmed

303

RAM Checksum bad

Zone

A test of the system's memory has failed

304

ROM checksum bad

Zone

A test of the system's executable memory has failed

305

System reset

Zone

The system has reset and restarted

306

Panel programming changed

Zone

The programmed configuration of the panel has changed

307

Self-test failure

Zone

The system has failed a self-test

308

System shutdown

Zone

The system has been shut down and has stopped functioning

309

Battery test failure

Zone

The system backup battery has failed a load test while the system was disarmed

310

Ground fault

Zone

The panel has detected a ground fault condition

311

Battery Missing/Dead

Zone

The system has detected that the backup battery is either missing or completely discharged.

312

Power Supply Overcurrent

Zone

The system power supply has reported an excessive current draw condition

313

Engineer Reset

User

The specified service person has issued a system reset

314

Primary Power Supply Failure

Zone

The system's primary power supply has failed a supervision test. Radio devices indicate this when the backup battery charging circuit has failed its supervision test

316

System Tamper

Zone

The system has been tampered with and may have been compromised

320

Sounder/Relay

Zone

A trouble condition exists in the system's sounder/relay circuit

321

Bell 1

Zone

A trouble condition exists in the primary bell circuit

322

Bell 2

Zone

A trouble condition exists in the secondary bell circuit

323

Alarm relay

Zone

A trouble condition exists in the system's alarm relay circuit

324

Trouble relay

Zone

A trouble condition exists in the system's trouble relay circuit

325

Reversing relay

Zone

The specified TELCO reversing relay has reported a trouble condition

326

Notification Appliance Ckt. # 3

Zone

A trouble condition exists in the bell #3 circuit

327

Notification Appliance Ckt. #4

Zone

A trouble condition exists in the bell #4 circuit

330

System Peripheral trouble

Zone

A system peripheral device has reported a trouble condition

331

Polling loop open

Zone

An open circuit condition has been detected on a polling loop while the system was disarmed

332

Polling loop short

Zone

A short circuit condition has been detected on a polling loop while the system was disarmed

333

Expansion module failure

Zone

A general failure condition has been detected on an expansion module while the system was disarmed

334

Repeater failure

Zone

A repeater in the system has reported a failure condition while the system was disarmed

335

Local printer out of paper

Zone

The printer attached to the panel has reported an Out Of Paper condition

336

Local printer failure

Zone

The printer attached to the panel has reported a failure condition

337

Exp. Module DC Loss

Zone

An expansion module has detected a DC power loss

338

Exp. Module Low Batt

Zone

An expansion module has detected a low battery condition

339

Exp. Module Reset

Zone

An expansion module has reset

341

Exp. Module Tamper

Zone

An expansion module has detected its taper switch has been faulted

342

Exp. Module AC Loss

Zone

An expansion module has detected the loss of AC power

343

Exp. Module self-test fail

Zone

An expansion module has failed a self-test

344

RF Receiver Jam Detect

Zone

An RF receiver has detected the presence of a jamming signal, preventing it from receiving normal signals from the system RF devices

345

AES Encryption disabled/ enabled

Zone

E345 AES Encryption has been disabledR345 AES Encryption has been enabled

350

Communication trouble

Zone

The system has experienced difficulties communicating with the central station

351

Telco 1 fault

Zone

The system has detected a fault on the primary dial-up line

352

Telco 2 fault

Zone

The system has detected a fault on the secondary dial-up line

353

Long Range Radio xmitter fault

Zone

A fault has been detected in the long range radio subsystem

354

Failure to communicate event

Zone

The system was unable to communicate an event to the central station

355

Loss of Radio supervision

Zone

The radio has not reported in its designated supervision interval

356

Loss of central polling

Zone

The radio has detected a loss in the polling signal from it's associated receiver

357

Long Range Radio VSWR problem

Zone

The Long Range Radio has reported a transmitter/antenna problem

358

Periodic Comm Test Fail /Restore

Zone

A periodic Communication path test has failed

370

Protection loop

Zone

The specified protection loop has reported a trouble condition

371

Protection loop open

Zone

The specified protection loop has reported an open-loop trouble condition

372

Protection loop short

Zone

The specified protection loop has reported a shorted-loop trouble condition

373

Fire trouble

Zone

A fire sensor has detected a trouble condition on the specified zone while the system was disarmed

374

Exit error alarm (zone)

Zone

An exit error condition has been reported for the specified alarm zone

375

Panic zone trouble

Zone

The system has detected a trouble condition on the panic zone

376

Hold-up zone trouble

Zone

The system has detected a trouble condition on the hold-up zone

377

Swinger Trouble

Zone

A fault has occurred on a zone that has been shut down due to excessive alarms

378

Cross-zone Trouble

Zone

The specified zone in a cross-zone configuration has faulted without a fault on its corresponding cross-zone in a specific time period

380

Sensor trouble

Zone

The specified sensor has reported a trouble condition

381

Loss of supervision - RF

Zone

The specified zone has failed to report in during its designated supervision period

382

Loss of supervision - RPM

Zone

An Remote Polled Module assigned to the specified zone has failed supervision

383

Sensor tamper

Zone

The tamper switch on the specified sensor has been faulted

384

RF low battery

Zone

The specified battery powered RF zone has reported a low battery condition

385

Smoke detector Hi sensitivity

Zone

A smoke detector's sensitivity level has drifted to the upper limit

386

Smoke detector Low sensitivity

Zone

A smoke detector's sensitivity level has drifted to the lower limit

387

Intrusion detector Hi sensitivity

Zone

An intrusion detector's sensitivity level has drifted to the upper limit

388

Intrusion detector Low sensitivity

Zone

An intrusion detector's sensitivity level has drifted to the lower limit

389

Sensor self-test failure

Zone

The specified sensor has failed a self-test

391

Sensor Watch trouble

Zone

A motion sensor has not been triggered within a pre-defined time interval

392

Drift Compensation Error

Zone

A smoke detector cannot automatically adjust its sensitivity

393

Maintenance Alert

Zone

The specified zone requires maintenance

394

CO Detector needs replacement

Zone

The specified Carbon Monoxide detector has reached end-of-life

400

Open/Close

User

The specified user has disarmed/armed the system

401

O/C by user

User

The specified user has disarmed/armed the system

402

Group O/C

User

A group of zones has been armed or disarmed

403

Automatic O/C

User

A partition has been automatically armed or disarmed

404

Late to O/C (Note: use 453 or 454 instead )

User

405

Deferred O/C (Obsolete- do not use )

User

406

Cancel

User

The specified user has cancelled the previously reported alarm condition

407

Remote arm/disarm

User

The specified user has armed or disarmed the system from off-premises

408

Quick arm

User

The specified user has quick-armed the system

409

Keyswitch O/C

User

The specified user has armed or disarmed the system using a keyswitch

411

Callback request made

User

A remote site (central station) has requested the panel call it back

412

Successful download/access

User

The configuration data of the system has been successfully downloaded

413

Unsuccessful access

User

A number of failed attempts have been made to remotely access the system

414

System shutdown command received

User

A central station has sent a system shutdown command to the panel

415

Dialer shutdown command received

User

A central station has sent a dialer shutdown command to the panel

416

Successful Upload

Zone

The configuration data of the system has been successfully uploaded

421

Access denied

User

The access control system has denied access to the specified user

422

Access report by user

User

423

Forced Access

User

The specified access control door has been forced open

424

Egress Denied

User

The access control system has denied egress to the specified user

425

Egress Granted

User

The access control system has granted egress for the specified user

426

Access Door propped open

Zone

The specified access control door has been held open

427

Access point Door Status Monitor trouble

Zone

The specified Access Point's Door Status Monitor has reported a trouble condition to the panel

428

Access point Request To Exit trouble

Zone

The specified Access Point's Request To Exit zone has reported a trouble condition to the panel

429

Access program mode entry

User

The access control system has been put into program mode

430

Access program mode exit

User

The access control system has exited program mode

431

Access threat level change

User

The access control system's threat level has been changed

432

Access relay/trigger fail

Zone

The specified access control output device has failed to operate properly

433

Access RTE shunt

Zone

The specified Request To Exit zone has been shunted and will no longer report activity

434

Access DSM shunt

Zone

The specified Door Status Monitor zone has been shunted and will no longer report activity

435

Second Person Access

User

A second person has accessed an access point conforming to Two-Man-Rule requirements

436

Irregular Access

User

441

Armed STAY

User

The specified user has armed the system in STAY mode

442

Keyswitch Armed STAY

User

The specified user has armed the system in STAY mode using a keyswitch

443

Armed with System Trouble Override

User

The specified user has armed the system while overriding a trouble condition

450

Exception O/C

User

The system has been armed or disarmed outside of the configured time window

451

Early O/C

User

The system has been disarmed/armed by the specified user before the configured time window has started

452

Late O/C

User

The system has been disarmed/armed by the specified user after the configured time window has ended

453

Failed to Open

User

The system has failed to have been disarmed during the designated time window

454

Failed to Close

User

The system has failed to be armed during the designated time window

455

Auto-arm Failed

User

The system has failed to automatically arm itself at the designated time

456

Partial Arm

User

The system has been only partially armed by the specified user

457

Exit Error (user)

User

The specified user has made an error exiting the premises after arming the system

458

User on Premises

User

A user has disarmed the system after an alarm has occurred

459

Recent Close

User

The system had been armed within the last xx minutes

461

Wrong Code Entry

Zone

462

Legal Code Entry

User

463

Re-arm after Alarm

User

464

Auto-arm Time Extended

Zone

A user has successfully requested that the system delay automatically arming

465

Panic Alarm Reset

User

The specified panic zone has been reset

466

Service On/Off Premises

User

A service person has entered or left the premises

501

Access reader disable

Zone

The credential reader on the specified access point has been disabled

520

Sounder/Relay Disable

Zone

The specified sounder or relay has been disabled

521

Bell 1 disable

Zone

The specified output for Bell 1 has been disabled

522

Bell 2 disable

Zone

The specified output for Bell 2 has been disabled

523

Alarm relay disable

Zone

The specified alarm relay has been disabled

524

Trouble relay disable

Zone

The specified trouble relay has been disabled

525

Reversing relay disable

Zone

The specified reversing relay has been disabled

526

Notification Appliance Ckt. # 3 disable

Zone

The specified output for Bell 3 has been disabled

527

Notification Appliance Ckt. # 4 disable

Zone

The specified output for Bell 4 has been disabled

531

Module Added

Zone

The specified access control module has been added to the system

532

Module Removed

Zone

The specified access control module has been removed from the system

551

Dialer disabled

Zone

The specified dialer has been disabled

552

Radio transmitter disabled

Zone

The specified radio transmitter has been disabled

553

Remote Upload/Download disabled

Zone

Remote configuration has been enabled

570

Zone/Sensor bypass

Zone

The specified zone or sensor has been bypassed

571

Fire bypass

Zone

The specified fire zone has been bypassed

572

24 Hour zone bypass

Zone

The specified 24 hour zone has been bypassed

573

Burg. Bypass

Zone

The specified burglary zone has been bypassed

574

Group bypass

Zone

A group of zones has been bypassed

575

Swinger bypass

Zone

The specified zone which has reported an excessive number of faults/restores in a short period of time has been bypassed

576

Access zone shunt

Zone

The specified zone in the access control system has been shunted and will no longer report activity

577

Access point bypass

Zone

The specified access point in the access control system has been bypassed and will allow the door to open (unsecured)

578

Vault Bypass

Zone

The specified vault zone has been bypassed

579

Vent Zone Bypass

Zone

The specified vent zone has been bypassed and will no longer report any activity

601

Manual trigger test report

Zone

A test report has been triggered manually

602

Periodic test report

Zone

A periodic test report has been triggered

603

Periodic RF transmission

Zone

A periodic RF path test report has been triggered

604

Fire test

User

The specified user has initiated a test of the fire alarm zones

605

Status report to follow

Zone

606

Listen-in to follow

Zone

The system is about to activate a 2-way audio session

607

Walk test mode

User

The specified user has placed the system into the walk-test mode for testing purposes

608

Periodic test - System Trouble Present

Zone

A periodic test has been triggered but the fire system has a trouble condition present

609

Video Xmitter active

Zone

A video look-in session is about to begin

611

Point tested OK

Zone

The specified point tested successfully

612

Point not tested

Zone

The specified point has not been tested

613

Intrusion Zone Walk Tested

Zone

The specified intrusion zone has been successfully walk-tested

614

Fire Zone Walk Tested

Zone

The specified fire zone has been successfully walk-tested

615

Panic Zone Walk Tested

Zone

The specified panic zone has been successfully walk-tested

616

Service Request

Zone

A request has been made for system servicing

621

Event Log reset

Zone

The event log has been reset and all stored events have been discarded

622

Event Log 50% full

Zone

The event log is 50% full

623

Event Log 90% full

Zone

The event log is 90% full

624

Event Log overflow

Zone

The event log has overflowed and events have been lost

625

Time/Date reset

User

The time and date have been reset to a new value by the specified user

626

Time/Date inaccurate

Zone

The system time and date is known to be in error

627

Program mode entry

Zone

The system has been placed into program mode

628

Program mode exit

Zone

The system has exited program mode

629

32 Hour Event log marker

Zone

630

Schedule change

Zone

The specified fire/burglary schedule has been changed

631

Exception schedule change

Zone

The time schedule for event reporting by exception has been changed

632

Access schedule change

Zone

The specified access control schedule has been changed

641

Senior Watch Trouble

Zone

A person has not activated a motion sensor in a specified period

642

Latch-key Supervision

User

A child has disarmed the system (after school)

651

Reserved for Ademco Use

Zone

652

Reserved for Ademco Use

User

653

Reserved for Ademco Use

User

654

System Inactivity

Zone

System has not been operated for x days

655

User Code X modified by Installer

User

The Installer has modified the specified User's code

703

Auxiliary #3

Zone

704

Installer Test

Zone

750

User Assigned

789

User Assigned

796

Unable to output signal (Derived Channel)

Zone

798

STU Controller down (Derived Channel)

Zone

900

Download Abort

Downloader ID

The specified Downloader ID has aborted a download sequence in progress

901

Download Start/End

Downloader ID

Downloader has started or ended a download sequence to the panel

902

Download Interrupted

Downloader ID

A download sequence has been interrupted

903

Device Flash Update Started/ Completed

Device

A code update for a device has started (E903) or completed successfully (R903)

904

Device Flash Update Failed

Device

A code update for a device has failed

910

Auto-close with Bypass

Zone

An auto-close sequence has been started and the specified zone has been bypassed

911

Bypass Closing

Zone

912

Fire Alarm Silence

Zone

The fire alarm has been silenced

913

Supervisory Point test Start/End

User

A fire supervisory device has been tested

914

Hold-up test Start/End

User

The specified user has started or ended a hold-up test

915

Burg. Test Print Start/End

User

The printed progress of a burglary test has been started or ended

916

Supervisory Test Print Start/End

User

The printed progress of a supervisory test has been started or ended

917

Burg. Diagnostics Start/End

Zone

A burglary system diagnostic test has been started or ended

918

Fire Diagnostics Start/End

Zone

A fire system diagnostic test has been started or ended

919

Untyped diagnostics

Zone

920

Trouble Closing (closed with burg. during exit)

User

921

Access Denied Code Unknown

User

Access has been denied because the system did not recognize the supplied access code as valid

922

Supervisory Point Alarm

Zone

The specified supervisory point has reported an alarm condition

923

Supervisory Point Bypass

Zone

The specified supervisory point has been bypassed

924

Supervisory Point Trouble

Zone

The specified supervisory point has reported a trouble condition

925

Hold-up Point Bypass

Zone

The specified hold-up point has been bypassed

926

AC Failure for 4 hours

Zone

There has been a loss of AC power for at least four hours

927

Output Trouble

Zone

The specified output has reported a trouble condition

928

User code for event

User

This message contains the ID of the user who triggered the previous event

929

Log-off

User

The specified user has logged-off of the system

954

CS Connection Failure

Zone

The specified CS connection has failed/restored

961

Rcvr Database Connection Fail/Restore

Zone

The connection to the receiver's database has failed/restored

962

License Expiration Notify

Zone

The product license has been terminated (7810PC)