Override a scheduled fence zone state

Override, shunt or lock out a fence zone from a Gallagher T20 Terminal.

A fence zone normally follows its alarm zone: it pulses when the alarm zone is armed, in the HV/LF mode its alarm zone sets. The override actions apply to one fence zone. Lockout can also be applied to all of a fence controller's fence zones from the Fences list. Arming or disarming the alarm zone itself changes every fence zone in it, except fence zones that are locked out, held by an On override, or on a fence controller that is in Service Mode or shunted.

Procedure

  1. Log on. If the fence controller list isn't showing, choose Fences from the Menu.

  2. Select the fence controller and press More.

  3. Select the fence zone and press More. The fence zone's details and actions display.

  4. Choose an action and press Select. The actions listed depend on your privileges.

Actions

Action
Use to...
Reverse

Override to On - High Voltage

Turn the fence zone on at high voltage, even if its alarm zone is disarmed.

Cancel overrides

Override to On - Low Feel

Turn the fence zone on in Low Feel, even if its alarm zone is disarmed.

Cancel overrides

Shunt zone

Mask the fence zone's alarms. Shunting is not a way to turn the fence on or off.

Unshunt zone

Lockout

Stop the fence zone pulsing so it can be worked on. See Lock out a fence zone.

Undo Lockout

Force arm alarm zone

Force arm the alarm zone this fence zone is assigned to. This arms the whole alarm zone, which energizes the fence zones in it. Locked-out fence zones stay off. Treat the rest as live.

Disarm alarm zone

Disarm alarm zone

Disarm the alarm zone this fence zone is assigned to. This disarms the whole alarm zone, not only this fence zone.

Arm the alarm zone, or Force arm alarm zone

An On override or a shunt stays in place until someone cancels it, at a terminal or in Command Centre. To cancel an On override from the T20, open the same fence zone and choose Cancel overrides. To cancel a shunt, choose Unshunt zone. A lockout can be undone only at the terminal that started it.

Shunt, lock out or disarm?

Action
Fence pulses
Use for

Shunt

Unchanged

Masking a faulty zone's alarms from site monitoring, for example during an alarm flood until a maintenance crew reaches site. Shunting only masks alarms and is not a way to turn the fence on or off, so treat it as live. To work on the fence, lock it out.

Lockout

No. Alarms are still raised.

Any work on the fence.

Disarm

No, unless an On override is in place or the fence controller is in Service Mode

Not for work on the fence. The zone pulses again when its alarm zone is armed.