Test alarm inputs

How alarm zone inputs are tested from a Gallagher T20 Terminal.

A test runs when Test Mode is selected for the alarm zone from the T20, or during disarming.

Test modes are set up in Command Centre for the inputs, the alarm zone, the Access Group, cardholders and the terminal. See Alarm Input Test Modes in the Command Centre Configuration Client user guide.

Scheduled test

A scheduled test is offered when you disarm, if you are authorized to test inputs. You can enter Test Mode or disarm as usual. If a test is due, it must be performed.

  1. Press Disarm, then log on. If the Alarm Zones screen displays, press Disarm All. Testing Scheduled displays, with the alarm zones whose inputs are to be tested.

  2. Press Yes to start an optional test, or Ok for a test you can't skip. A countdown shows the time set to complete the test, and you can extend it. The terminal beeps every second while in Test Mode.

  3. Activate each input in the test, for example PIRs and duress buttons.

  4. Press End. Testing succeeded displays, or Testing failed with the inputs that failed.

  5. Press Ok.

Unscheduled test

An unscheduled test leaves the alarm zone's state unchanged. No alarms are raised while it runs.

  1. Log on and choose Test from the Menu.

  2. Select the alarm zone and press Test, or press Test All. A countdown shows the time set to complete the test, and you can extend it. The terminal beeps every second while in Test Mode.

  3. Activate each input in the test.

  4. Press End. Testing succeeded displays, or Testing failed with the inputs that failed.

  5. Press Ok.

After either test, if set up in Command Centre, each failed input is reported to the alarm monitoring station and emailed to the manager.