Configure HBUS biasing and termination

Learn how to configure HBUS biasing and termination for Gallagher Fibre Transceivers.

Read Gallagher Fibre Transceiver if you are new to the product.

Configure each HBUS run with one biasing source and termination at both ends. This prevents unreliable communication during commissioning.

HBUS runs

Each Fibre Transceiver starts a separate HBUS run. Treat each run as an independent entity.

  • One biasing source per segment

  • Termination at each end of the run

A segment is an HBUS run on one physical electrical path. A fibre section separates segments. Each segment needs its own single biasing source.

Biasing

Biasing supplies voltage to an HBUS run. Communicating devices pull this voltage down.

More than one biasing source causes signal contention. Configure only one source for each segment.

Controller 6000 connections

A Controller 6000 is always a biasing source. Turn off biasing on a Fibre Transceiver connected to a Controller 6000.

Use DIP switch 5 for channel 1 or DIP switch 6 for channel 2. Terminate the Controller 6000 and Fibre Transceiver when they sit at opposite ends of the run.

See Fibre Transceiver specifications for switch positions.

Incorrect configurations

Mistake
Consequence

No biasing on a segment

The HBUS section does not work reliably

Two biasing sources on a segment

Signal contention causes unreliable communication

Termination in the middle of the run

The affected section has reduced reliability

Missing termination at the ends

Reflections cause unreliable communication