Configure HBUS biasing and termination
Learn how to configure HBUS biasing and termination for Gallagher Fibre Transceivers.
Configure each HBUS run with one biasing source and termination at both ends. This prevents unreliable communication during commissioning.
HBUS runs
Each Fibre Transceiver starts a separate HBUS run. Treat each run as an independent entity.
One biasing source per segment
Termination at each end of the run
A segment is an HBUS run on one physical electrical path. A fibre section separates segments. Each segment needs its own single biasing source.
Biasing
Biasing supplies voltage to an HBUS run. Communicating devices pull this voltage down.
More than one biasing source causes signal contention. Configure only one source for each segment.
Controller 6000 connections
A Controller 6000 is always a biasing source. Turn off biasing on a Fibre Transceiver connected to a Controller 6000.
Use DIP switch 5 for channel 1 or DIP switch 6 for channel 2. Terminate the Controller 6000 and Fibre Transceiver when they sit at opposite ends of the run.
See Fibre Transceiver specifications for switch positions.
Incorrect configurations
No biasing on a segment
The HBUS section does not work reliably
Two biasing sources on a segment
Signal contention causes unreliable communication
Termination in the middle of the run
The affected section has reduced reliability
Missing termination at the ends
Reflections cause unreliable communication
🔗 Related
Fibre Transceiver communication issues provides fault-finding diagrams.
Fibre Transceiver specifications identifies each switch function.
Connect Fibre Transceiver power and ground explains required ground connections.