Fibre Transceiver communication issues

Diagnose HBUS communication issues caused by incorrect biasing, termination, or dirty fibre connections.

Read Configure HBUS biasing and termination for the required configuration.

Use these diagrams to identify biasing and termination faults. Clean disconnected fibre terminations professionally if communication remains intermittent.

Check the Controller connection

This diagram shows four Fibre Transceivers linking one Controller and five Fence Controllers.

Fibre transceiver biasing and termination, fault finding diagram

The Controller is always a biasing source. Turn off biasing on its connected Fibre Transceiver. Terminate both devices when they are at opposite ends of the HBUS run.

Check each HBUS run

Each blue line from a Fibre Transceiver is a separate HBUS run. Each run needs one biasing source and termination at both ends.

  • Missing biasing causes unreliable HBUS communication

  • Incorrect termination reduces reliability

Fault-finding: biasing and termination states at the device end, biased-not-terminated versus biased-and-terminated

Check biasing sources

Biasing supplies voltage to the HBUS run. Communicating devices pull this voltage down.

A segment is an HBUS run on one physical electrical path. Fibre sections separate segments. Each segment needs exactly one biasing source.

N11/N12 termination diagram