Legacy I/O devices
Identify legacy GBUS and Local BUS hardware, support limits, and HBUS replacements.
Identify legacy Gallagher hardware that current Command Centre versions no longer support. Use this information to plan an HBUS replacement.
Overview
The hardware listed on this page is no longer supported in the current versions of Command Centre. It is documented so you can identify what is on an existing site and know what the upgrade path looks like.
Support cutoff versions
GBUS
vEL9.00
Local BUS
vEL8.0
⚠️ Check the I/O protocol family before quoting a Command Centre upgrade. A site running GBUS expansion hardware cannot upgrade its Command Centre server past vEL9.00 without first replacing the I/O hardware. A site running Local BUS hardware is capped at vEL8.0.
GBUS hardware
C200680
GBUS 8 Input Expansion Board
C200684
GBUS 8 In 4 Out I/O Expansion
C200688
GBUS 16 In 16 Out High Density I/O
C200660
GBUS URI 8 In 2 Out Cardax IV
C200665
GBUS URI 4 In 2 Out Wiegand
C200601, C200602
GBUS Remote Arming Terminal
HBUS equivalents
C200680 (8 Input)
C300680 (8 Input)
C200684 (8 In 4 Out)
C300684 (8 In 4 Out)
C200688 (16 In 16 Out)
C300688 (16 In 16 Out)
C200660 (URI 8 In 2 Out)
C300660 (Door Module)
C200665 (URI 4 In 2 Out Wiegand)
C300665 (Door Module - Wiegand)
Local BUS hardware
Local BUS URI 6 In 2 Out Cardax IV or Wiegand
Local BUS Relay Interface 20 Out
Local BUS I/O Interface 15 In 5 Out
Local BUS FT Reader I/O Interface 24 In 8 Out 16 Cardax IV Readers
Cardax FT Digital Camera
Local BUS predates GBUS. If a site still runs Local BUS hardware, it is most likely running on Cardax FT era controllers.
Upgrade options
GBUS sites. Replace each GBUS board with the equivalent HBUS board. Verify the replacement against its install note. Enable HBUS on the controller. Then bring the new boards online.
Local BUS sites. A Local BUS to HBUS migration is a controller refresh. Scope a full controller and I/O replacement.