HBUS I/O device capabilities
Understand HBUS I/O device functions, identification, replacement, and firmware management.
HBUS I/O devices connect monitoring and control equipment. They offer flexible functions, automatic identification, and managed firmware.
Connecting equipment to the security system
HBUS I/O devices connect monitoring and control equipment to the security system. Gallagher provides a range of device sizes for common requirements.
HBUS I/O devices connect back to a Controller 6000 or Controller 7000.

Functions are not pre-assigned
Inputs and output relays in Gallagher Command Centre do not have pre-assigned functions. Any input can monitor doors, detectors, or plant equipment. Assign the required function during system configuration.
Devices are uniquely serialized
HBUS units are uniquely serialized. When connected to a Controller 6000 or Controller 7000, each device identifies and configures itself.
⚠️ If an HBUS I/O device is replaced, Command Centre must be configured to recognize the replacement part. Otherwise it cannot communicate with the Controller. The serial number changes with the board, so a like-for-like swap that is wired correctly will still report a comms fault until Command Centre is updated.
Firmware is managed automatically
The controller automatically updates device firmware to match its firmware version. No user interaction is required.
Last updated
Was this helpful?