HBUS I/O devices
Identify current HBUS I/O devices, power requirements, and cable-run limits.
Identify currently supported HBUS I/O hardware. Use the variants and topology rules to plan an installation.
Overview
Gallagher Security provides I/O devices that connect to a controller through the proprietary HBUS protocol.
HBUS units are uniquely serialized. When connected, the controller identifies and configures each device.
⚠️ If an HBUS I/O device is replaced, Command Centre must be configured to recognize the replacement part. Otherwise it cannot communicate with the Controller.
Variants
Power differs across the range. The 8 In and 8 In 4 Out boards and both door modules are HBUS-powered. The HBUS 16 In 16 Out Board requires a separate external 12 V DC supply, and both hubs require separate external power.
📎 Part-number note: the 4 In 2 Out Wiegand door module is C300665 (install note 3E4597). C300660 is a different part, the HBUS 8 In 2 Out Door Module (install note 3E3472).
Topology rules
Maximum 24 HBUS units per cable run.
Maximum cable distance 500 m from the Controller 7000. This requires Command Centre vEL9.40 or later.
Topology must be daisy-chain only. T-junctions and star topologies are not permitted between HBUS devices.
End devices on each cable run must be terminated with 120 ohm resistance.
Ground shielded cable at the controller end only.
Recommended cables
CAT 5e or better
4 twisted pair, 2 x 0.2 mm² (24 AWG)
500 m
50 m
Belden 9842 (shielded)
2 twisted pair, 2 x 0.2 mm² (24 AWG)
500 m
50 m
SEC472
4 x 0.2 mm² untwisted (24 AWG)
400 m
50 m
SEC4142
4 x 0.4 mm² untwisted (21 AWG)
400 m
100 m
C303900/C303901 Gallagher HBUS Cable
2 twisted pair data + 2 x 0.75 mm² power
500 m
200 m