FTP Upgrading legacy controllers
A guide on how to connect to the legacy controllers (3000, 5000, 5000GL) to manually upgrade the firmware through an FTP connection.
⚠️ Pre-condition: Any legacy controllers (3000, 5000, 5000GL) that are lower than version 5.21 will need to be at 5.20 or 5.21 before they can be upgraded to later versions (up to 8.20, as they are not supported past this version). This can normally be done via Command Centre. This FTP procedure is the manual fallback.
⚠️ CAUTION: Read the entire procedure before carrying it out.
FTP Upgrade Procedure
1. Create a folder for the upgrade files
Create a folder that is easy to browse to from a command prompt, for example:
c:\ftp2. Copy the firmware files to the folder
Copy _NEW_APP.CFG and BTxxxxx.EXE from the Gallagher Software CD > Other Device Software folder, to the new folder created above.
3. Set the DIP switch
Ensure Controller DIP switch 1 is ON.
4. Web-browse to the Controller
Open a web browser and enter the Controller IP address followed by /debug:
When the controller is in 2 flashes after rebooting, the login details for web-browse are:
diagnostic
[REDACTED] (contact Tech Support)
If the controller is in 1 flash, you need the site serial number to generate the password. This requires Tech Support involvement.
5. Start the FTP Server on the Controller
Click Database Manager then click Start FTP Server. (Alternatively, in the properties of the Controller in Command Centre, click Start FTP Server.)
⚠️ 15-second timeout: This login will time out after 15 seconds. You need to get past Step 6 before then or you will be disconnected.
6. Connect to the Controller via FTP
From the command prompt:
(Substitute the actual Controller IP address.)
When prompted, enter the FTP username cardax. Contact Tech Support for the FTP credentials.
7. Switch FTP to binary mode
Type bin (without the quotes) and press Enter. This puts FTP in Binary mode.
8. Upload the firmware files
Use the following commands to upload the files to the Controller (this assumes the files are in the folder that FTP was launched from):
The BT750118 firmware file takes approximately 42 seconds to transfer. Do not interrupt.

9. Reboot the Controller
Reboot the Controller. It should now be upgraded to the required version vBTxxxxx.
10. Resync databases
When the Controller is back online, re-sync the databases from Command Centre.
Optional - free up space if required
If required, delete the following file to ensure enough space is free:
PART.CDB
103,000 bytes
To delete the file while using FTP:
🧑🔧 Perform this deletion step via the FTP session before uploading the firmware files if the controller reports insufficient space.
🔗 Related
Controllers - Legacy. Variants and lifecycle.
Controllers Legacy - Limits. Hardware capacity per model.
Last updated