Controllers Legacy - Limits

⚠️ Legacy controllers are not supported above CC v8.20. See Controllers - Legacy.

Bus distances

Bus
Maximum distance

Local Bus (5000 and 5000GL only)

500 metres

GBUS

1,220 metres


Parts limits (from SCR901)

Controller
Typical parts

C3000

500 typical parts

C5000GL

1,000 typical parts

"Typical parts" describes the average part memory usage. Heavy-weight parts will consume more memory (reducing the limit). Lighter parts will occupy less memory (allowing more parts).


Network connections (3000, 5000, 5000GL)

Direction
Limit

Incoming connections

30

Outgoing connections

30


3000-8R limits

  • 8 CardaxIV readers, or 4 Wiegand readers

  • 8 GBus devices and 4 RATs

  • Controls up to 8 doors

  • Stores up to 46,000 cardholders (depending on allocation settings)

  • No support for Local Bus


3000-4R limits

  • 4 CardaxIV readers, or 2 Wiegand readers

  • 8 GBus devices and 4 RATs

  • Controls up to 4 doors

  • Stores up to 46,000 cardholders

  • No support for Local Bus


5000 limits

  • 16 Local Bus devices (access control and alarm monitoring)

  • 8 doors

  • 46,000 cardholders (depending on allocation settings)


5000GL limits

  • Up to 8 doors

  • Up to 92,000 cardholders (depending on database allocation settings)

  • Bus options:

    • 16 Local Bus devices, 8 GBus units, and 4 RATs, or

    • 16 GBus devices and 8 RATs


Capacity allocation reference

For approximations of various database allocation settings for legacy controllers, refer to Command Centre Classic Online Help: Altering Controller memory between Cards and Events.

For C6000 limits (current product family), see Controller 6000 - Limits.


🔗 Related

Last updated

Was this helpful?