Controllers Legacy - Limits
⚠️ Legacy controllers are not supported above CC v8.20. See Controllers - Legacy.
Bus distances
Local Bus (5000 and 5000GL only)
500 metres
GBUS
1,220 metres
Parts limits (from SCR901)
C3000
500 typical parts
C5000GL
1,000 typical parts
"Typical parts" describes the average part memory usage. Heavy-weight parts will consume more memory (reducing the limit). Lighter parts will occupy less memory (allowing more parts).
Network connections (3000, 5000, 5000GL)
Incoming connections
30
Outgoing connections
30
3000-8R limits
8 CardaxIV readers, or 4 Wiegand readers
8 GBus devices and 4 RATs
Controls up to 8 doors
Stores up to 46,000 cardholders (depending on allocation settings)
No support for Local Bus
3000-4R limits
4 CardaxIV readers, or 2 Wiegand readers
8 GBus devices and 4 RATs
Controls up to 4 doors
Stores up to 46,000 cardholders
No support for Local Bus
5000 limits
16 Local Bus devices (access control and alarm monitoring)
8 doors
46,000 cardholders (depending on allocation settings)
5000GL limits
Up to 8 doors
Up to 92,000 cardholders (depending on database allocation settings)
Bus options:
16 Local Bus devices, 8 GBus units, and 4 RATs, or
16 GBus devices and 8 RATs
Capacity allocation reference
For approximations of various database allocation settings for legacy controllers, refer to Command Centre Classic Online Help: Altering Controller memory between Cards and Events.