For the complete documentation index, see llms.txt. This page is also available as Markdown.

Test controller connections

Test Controller 7000 network connectivity, port 1072, server communication, and diagnostics.

📋 Prerequisites: Know the controller and server IP addresses. If the controller has never come online, work through Bringing Online and Networking first.

A toolkit for diagnosing network connectivity issues between a C7000 controller and the Command Centre server.

This procedure also applies to Controller 7000 SDC.

Best practice: The majority of these tests are best run from the controller's network connection point using a laptop, back to the server. Ideally, configure the laptop with the same IP settings as the controller and plug it into the same network connection point. From version 9.30 onwards, the controller can perform these tests itself (see Network Connectivity Tools below).


Ping

How do I confirm a controller can reach the server on the network?

C:\>ping <controller IPAddress>
C:\>ping <server IPAddress>

A reply confirms a network connection exists. It also populates the ARP cache (required before running ARP).

Ping may fail if:

  • No route exists to the controller

  • ICMP protocol is disabled on the site network

If ping is disabled, the test may fail even when a valid network connection exists.

Check the Link Light: the green LED next to the Ethernet port on the controller should be solid on.

Note: If ping returns an IPv6 address, force IPv4 with: ping -4 <HostName>

Cross-subnet: If the controller is on a different subnet to the server, the switch the controller is plugged into must reply to pings. The controller pings the gateway to confirm connectivity before transmitting data to the server.


Listen port

Which tools test port 1072?

Default communication port: Port 1072 (defined as the Listen Port in the Gallagher Registry).

Unless a unique Listen Port has been configured, port 1072 is always used after installing Command Centre.

Note: If the site uses a non-standard listen port, the controller must first connect to the server to pick up that port.


Telnet

Tests TCP port 1072 (controller-to-server and controller-to-controller communication).

Important: Run the telnet test in both directions: controller to server and server to controller.

Note: If you get "'telnet' is not recognized", install from Control Panel > Programs and Features > Turn Windows features on or off. Install both Telnet Client and Telnet Server.

Interpretation:

Result
Meaning

Screen blanks, cursor flashes top-left

Port is OPEN (OK)

Cursor returns to C: prompt

Port is OPEN (OK) — may see connection-lost message or alarm if controller is online

Connection refused / error message

Port is BLOCKED (FAIL)

If blocked, check:

  1. Windows Firewall or third-party firewall. See Firewall Issues.

  2. Ask IT if the port is blocked at Switch/Router level.

  3. Anti-virus. Some corporate AV software prevents controller connections; temporarily disable to test.


Telnet alternative: PowerShell TNC (preferred)

Example: tnc 10.20.82.199 -p 1072

TNC command result

Advantages over Telnet:

  1. No Telnet client installation required

  2. Shows which Server IP and Network Adapter are used to communicate with the controller


Network Connectivity Tools (v9.30+)

Available from CC version 9.30 onwards, directly from the controller's web pages (both the Web Config and Debug pages).

Access: Click the Network Connectivity Tools link in the controller's web interface.

Network Connectivity Tools entry

The dialog:

Network Connectivity Tools dialog

By default, the dialog pre-fills the Gallagher Controller Service listen port (1072). Enter the server's IP address and click ConnectToIPAddress.

Successful connection to port 1072:

Successful connection

Failed connection (port not responding):

Failed connection

The tool is also accessible from the Debug main page:

Network Connectivity Tools from debug page

ARP

Run after pinging the controller. Confirms you are receiving a reply from an actual Gallagher controller.

Find the Internet Address you pinged. If the Physical Address starts with 00-90-1d it is a Gallagher controller.


Netstat

How do I confirm another application is not holding port 1072?

CC version 9.00 and above: one connection

Netstat v8.50+ result

From CC v8.50, there is only ONE connection established (controller to server). This is expected and correct behavior.

Checking the server is listening on port 1072

TCP netstat port 1072 listening

Run netstat -ano. The server should show LISTENING on port 1072, with a PID. Confirm that PID belongs to the FT Controller Service in Windows Task Manager.

Task Manager PID list

Important: If the PID of 'FT Controller Service' does NOT match the PID using port 1072, another application is locking port 1072 and causing the controller to fail to come online.

Port conflict — wrong PID

Solutions if another application has port 1072:

  • Option 1: Get the third-party application to change or stop using port 1072.

  • Option 2: Change the listen port of the server-controller communication to a custom port (see the Listen Ports for Controllers documentation).


Web browsing the controller

Directly browse the controller's web interface to confirm IP configuration, verify certificates and keys, check the error log, and confirm the node number.

URL format: {controller-ip}/debug. (trailing full stop is required)

Example: 172.16.243.56/debug.

Credentials:

Condition
Logon
Password

Controller in 2-flash state

diagnostic

[REDACTED] (default - contact Tech Support)

Controller in 1-flash state

diagnostic

[REDACTED] (site-specific value based on Site Serial number - contact Tech Support)

CC v8.40+

diagnostic

May be a configured password - check with Tech Support

Key diagnostic pages:

TCPSender. Primary page for confirming TCP/IP settings. Check the "Server IP" field. If it does not match the actual server IP, the controller will not come online. Active sessions show if the server is connected.

TCPExchange. Confirms keys and certificates are valid and the correct Master certificate is selected (must match the Certificate setting on the Controller's Setup tab in CC). Active sessions show if the controller is connected to the server.

Errorlog. Check as a last resort for recurring errors or restarts.

Node Number. Verify the node number on the web page matches the node number in Command Centre.

To find the Node Number in CC:

  1. Open Controller Properties and select the Setup tab.

  2. Hold Ctrl and double-click with the left mouse button in a clear area of the Setup tab.

  3. A popup displays the controller's node number.

Node number popup in CC

🔗 Related

Last updated

Was this helpful?