Run LED diagnostics and shutdown codes

Diagnose Controller 7000 startup states and shutdown events using Run LED patterns and codes.

Two diagnostic reference tables for Gallagher controllers: the Run LED flash states (visible on the physical controller) and the shutdown codes (found in the controller error log or Command Centre event messages).

This reference also applies to Controller 7000 SDC.


Run LED flash states

What does the Run LED flash pattern mean?

The red Run LED (D9) flashes to indicate the controller's operating status.

Flash
Sequence
Meaning

Slow

2000 ms on, 1000 ms off

Controller is searching for software FTS files

Fast

130 ms on, 130 ms off (4 Hz flash)

Initialising

1 Flash

500 ms on, 500 ms off (1 Hz flash)

Normal running

2 Flash

2 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)

Controller has an IP but no configuration, or has been configured incorrectly

3 Flash

3 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)

Controller requires an IP address. Ensure BootP Service (CCFTBPS.exe) is running, the controller is configured correctly, and it has connected to the network

4 Flash

4 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)

No private key or certificate loaded. Note: this can only be reset by the factory of manufacture.

5 Flash

5 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)

Invalid private key or certificate loaded, or key and certificate do not match the controller serial number. See DIP Switch 8 Recovery or contact Gallagher Tech Support.

6 Flash

6 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)

The controller has dropped its code. See DIP Switch 8 Recovery or contact Gallagher Tech Support.

7 Flash

7 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)

USB upgrade complete. Remove the USB drive to complete installation

(no flash number)

450 ms on, 50 ms off (2 Hz flash)

Controller Resetting

Short flash / long flash (1 s cycle)

100 ms on, 250 ms off

Boot code monitor running, network unplugged


Shutdown codes

Where do I find shutdown codes, and what do they mean?

Every time a controller shuts down, an SC code is recorded in the controller's error log (accessible via web browse) and may appear in Command Centre event messages.

Shutdown Code
Meaning
Fault or Normal
Likely Cause

0

Normal Termination (debug)

Normal

—

1

Remote Reset Request

Normal

Reset request after a code download

2

Power Fail

Normal

Power has failed

3

Hardware watchdog timeout

Software or hardware fault

S/W or H/W fault

4

Startup Failed

Software fault

Corrupt version of controller software

5

Configuration Failed

Fault

Invalid configuration

6

Out of Memory

Fault

Software bug, or too much activity

7

Assertion

Fault

Software bug, should only occur in debug versions

8

RAM error

Hardware fault

Faulty RAM chip

9

Code checksum error

Fault

Controller code has been corrupted

10

FTP server running

Normal

Controller was started with the /FTP parameter

11

Uncaught exception

Software fault

Depends on the exception

12

Caught exception

Software fault

Depends on the exception

255

Undefined Fault

Fault

Almost anything

Which codes point to a hardware fault versus normal behavior?

Troubleshooting: Repeated SC codes 3, 6, 8, or 255 in the error log point to hardware faults or memory corruption. SC 4 and 9 with repeated occurrences suggest corrupt firmware, so reapply firmware. SC 5 (Configuration Failed) is commonly caused by pushing configuration that is too large for the controller's current capacity limits.