Run LED diagnostics and shutdown codes
Diagnose Controller 7000 startup states and shutdown events using Run LED patterns and codes.
Two diagnostic reference tables for Gallagher controllers: the Run LED flash states (visible on the physical controller) and the shutdown codes (found in the controller error log or Command Centre event messages).
This reference also applies to Controller 7000 SDC.
Run LED flash states
What does the Run LED flash pattern mean?
The red Run LED (D9) flashes to indicate the controller's operating status.
Slow
2000 ms on, 1000 ms off
Controller is searching for software FTS files
Fast
130 ms on, 130 ms off (4 Hz flash)
Initialising
1 Flash
500 ms on, 500 ms off (1 Hz flash)
Normal running
2 Flash
2 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)
Controller has an IP but no configuration, or has been configured incorrectly
3 Flash
3 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)
Controller requires an IP address. Ensure BootP Service (CCFTBPS.exe) is running, the controller is configured correctly, and it has connected to the network
4 Flash
4 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)
No private key or certificate loaded. Note: this can only be reset by the factory of manufacture.
5 Flash
5 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)
Invalid private key or certificate loaded, or key and certificate do not match the controller serial number. See DIP Switch 8 Recovery or contact Gallagher Tech Support.
6 Flash
6 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)
The controller has dropped its code. See DIP Switch 8 Recovery or contact Gallagher Tech Support.
7 Flash
7 flashes, then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)
USB upgrade complete. Remove the USB drive to complete installation
(no flash number)
450 ms on, 50 ms off (2 Hz flash)
Controller Resetting
Short flash / long flash (1 s cycle)
100 ms on, 250 ms off
Boot code monitor running, network unplugged
Shutdown codes
Where do I find shutdown codes, and what do they mean?
Every time a controller shuts down, an SC code is recorded in the controller's error log (accessible via web browse) and may appear in Command Centre event messages.
0
Normal Termination (debug)
Normal
—
1
Remote Reset Request
Normal
Reset request after a code download
2
Power Fail
Normal
Power has failed
3
Hardware watchdog timeout
Software or hardware fault
S/W or H/W fault
4
Startup Failed
Software fault
Corrupt version of controller software
5
Configuration Failed
Fault
Invalid configuration
6
Out of Memory
Fault
Software bug, or too much activity
7
Assertion
Fault
Software bug, should only occur in debug versions
8
RAM error
Hardware fault
Faulty RAM chip
9
Code checksum error
Fault
Controller code has been corrupted
10
FTP server running
Normal
Controller was started with the /FTP parameter
11
Uncaught exception
Software fault
Depends on the exception
12
Caught exception
Software fault
Depends on the exception
255
Undefined Fault
Fault
Almost anything
Which codes point to a hardware fault versus normal behavior?
Troubleshooting: Repeated SC codes 3, 6, 8, or 255 in the error log point to hardware faults or memory corruption. SC 4 and 9 with repeated occurrences suggest corrupt firmware, so reapply firmware. SC 5 (Configuration Failed) is commonly caused by pushing configuration that is too large for the controller's current capacity limits.
🔗 Related
DIP Switch 8 Recovery. Recovery for 4-flash, 5-flash, 6-flash, and solid-on states.
Certificates and Keys. Why a 4-flash or 5-flash state indicates a key or certificate problem.
Limits. Capacity limits behind an SC 5 (Configuration Failed).