> For the complete documentation index, see [llms.txt](https://help.security.gallagher.com/knowledge-hub/llms.txt). Markdown versions of documentation pages are available by appending `.md` to page URLs; this page is available as [Markdown](https://help.security.gallagher.com/knowledge-hub/products/cc-hardware/controllers/controller-7000-and-7000-sdc/reference/controller-7000-limits.md).

# Controller 7000 limits

Reference Controller 7000 capacity limits for hardware, configuration, and connected devices.

Full hardware specifications, capacity limits, and feature comparisons for the C7000 controller family (and C6000 for cross-reference).

***

## Variants and CC version support

### C7000 Single Door (SDC) variants

| Part #  | Description                                | Supported from                                   |
| ------- | ------------------------------------------ | ------------------------------------------------ |
| C400020 | Controller 7000 Single Door, PoE+, RS485   | vEL8.70.2078 (MR3), vEL8.80.1025 (MR1), vEL8.90+ |
| C400021 | Controller 7000 Single Door, PoE+, Wiegand | vEL8.70.2078 (MR3), vEL8.80.1025 (MR1), vEL8.90+ |
| C400010 | Controller 7000 Single Door, RS485         | vEL8.70.2078 (MR3), vEL8.80.1025 (MR1), vEL8.90+ |
| C400011 | Controller 7000 Single Door, Wiegand       | vEL8.70.2078 (MR3), vEL8.80.1025 (MR1), vEL8.90+ |

### C7000 variants

| Part #  | Variant              | Supported from CC version                                                         |
| ------- | -------------------- | --------------------------------------------------------------------------------- |
| C400100 | 7000 Standard        | vEL9.00.1291 (Full Release)                                                       |
| C400110 | 7000 Starter         | vEL9.00.3371 (MR7) / vEL9.10.3194 (MR6) / vEL9.20.2337 (MR3) / vEL9.30.1871 (MR1) |
| C400101 | 7000 Enhanced        | vEL9.00.1291 (Full Release)                                                       |
| C400111 | 7000 2 Door          | vEL9.00.3371 (MR7) / vEL9.10.3194 (MR6) / vEL9.20.2337 (MR3) / vEL9.30.1871 (MR1) |
| C400112 | 7000 2 Door Enhanced | vEL9.00.3371 (MR7) / vEL9.10.3194 (MR6) / vEL9.20.2337 (MR3) / vEL9.30.1871 (MR1) |
| C405101 | 7000 High Sec        | vEL9.20.1043 (Full Release)                                                       |

***

## Physical limits

* **HBUS Distance:** 500 metres
* **GBUS:** Not supported on C7000 (no GBUS)

***

## Network

* C7000 Standard/Starter/2 Door: 10/100 Ethernet
* C7000 Enhanced / High Sec: Dual Gigabit Ethernet ports
* C7000 Single Door (PoE+ models): PoE+ powered
* Encryption: **256-bit AES symmetric** for Controller-to-Server and Inter-Controller communications

***

## RS-485 port protocol support

Protocols: HBUS, OSDP, Aperio, Schlage, Sensor bus

* Schlage: available from v9.00
* Sensor bus: available from v9.00 MR6, v9.10 MR5, v9.20 MR2

***

## Key capacity limits (C7000)

| Limit                 | Value                                                                                     |
| --------------------- | ----------------------------------------------------------------------------------------- |
| Cardholders           | 2,000,000 (note: Mobile Credentials consume more space than a standard cardholder record) |
| Offline Event Storage | 1,000,000 events                                                                          |
| Alarm Zones           | 256                                                                                       |
| Access Groups         | 2,000                                                                                     |
| HBUS Devices          | 80                                                                                        |
| Elevator Cars         | 10 cars, no floor limit                                                                   |
| Maximum Doors         | 24 (note: only 10 doors available unless licensing is added to extend this - v9.40+)      |

***

## Capacity comparison table

| Capacity Support        | C6000 Standard         | C6000 High Sec         | C7000 Single Door | C7000 Standard         | C7000 High Sec         |
| ----------------------- | ---------------------- | ---------------------- | ----------------- | ---------------------- | ---------------------- |
| Maximum Inputs          | 24 (expandable to 280) | 24 (expandable to 280) | 6                 | 24 (expandable to 536) | 24 (expandable to 536) |
| Maximum Outputs         | 8 (expandable to 264)  | 8 (expandable to 264)  | 2                 | 8 (expandable to 520)  | 8 (expandable to 520)  |
| Maximum Doors           | 10 (recommended)       | 10 (recommended)       | 1                 | 24‡                    | 24‡                    |
| Maximum Readers         | 20                     | 20                     | 10                | 48                     | 48                     |
| Maximum Alarm Terminals | 10                     | 10                     | 20\*              | 20\*                   | 20\*                   |
| Maximum Stored Events   | 80,000                 | 80,000                 | 1,000,000         | 1,000,000              | 1,000,000              |
| Maximum Cardholders     | 500,000                | 500,000                | 2,000,000         | 2,000,000              | 2,000,000              |
| Maximum Alarm Zones     | 256                    | 256                    | 256               | 256                    | 256                    |
| Maximum Active Alarms   | 100                    | 100                    | 1,000             | 1,000                  | 1,000                  |

\*Only 10 simultaneous logins allowed for Alarm Terminals.\
‡Only 10 doors available unless licensing is added (v9.40+).

***

## Hardware features comparison

| Hardware Feature                             | C6000 Standard                           | C6000 High Sec                           | C7000 Single Door                      | C7000 Standard                         | C7000 High Sec                         |
| -------------------------------------------- | ---------------------------------------- | ---------------------------------------- | -------------------------------------- | -------------------------------------- | -------------------------------------- |
| Onboard Ethernet                             | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| Max Ethernet Speed                           | 10/100Mbps                               | 10/100/1000Mbps                          | 10/100Mbps                             | 10/100Mbps                             | 10/100/1000Mbps                        |
| Embedded Processor                           | ARM9                                     | ARM9                                     | NXP i.MX8x                             | NXP i.MX8x                             | NXP i.MX8x FIPS                        |
| Memory                                       | 64MB RAM / 128MB NAND                    | 64MB RAM / 128MB NAND                    | 512MB RAM / 4GB eMMC                   | 512MB RAM / 4GB eMMC                   | 512MB RAM / 4GB eMMC                   |
| RS-485 Downstream Ports                      | YES (2 ports)                            | YES (2 ports)                            | YES (1 port)                           | YES (2 ports)                          | YES (2 ports)                          |
| RS-485 Max Speed                             | 1Mbps                                    | 1Mbps                                    | 1Mbps                                  | 1Mbps                                  | 1Mbps                                  |
| PoE Support                                  | Yes, non-native                          | NO                                       | Yes, PoE+ variants                     | NO                                     | NO                                     |
| Dual Ethernet (single MAC)                   | NO                                       | NO                                       | NO                                     | NO                                     | YES‡                                   |
| True Dual Ethernet (two MACs)                | NO                                       | Single MAC                               | NO                                     | NO                                     | YES                                    |
| Ethernet Bridging                            | NO                                       | NO                                       | NO                                     | NO                                     | YES†                                   |
| Peer-to-Peer Communications                  | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| Peer-to-Peer Limit                           | 60                                       | 60                                       | 100\*                                  | 100\*                                  | 100\*                                  |
| Virtual Outputs                              | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| Upstream Encryption                          | AES 256bit                               | AES 256bit                               | AES 256bit                             | AES 256bit                             | AES 256bit                             |
| Encryption to Field Devices                  | ECC 256bit Auth / AES 128bit Symmetric   | ECC 256bit Auth / AES 128bit Symmetric   | ECC 256bit Auth / AES 128bit Symmetric | ECC 256bit Auth / AES 128bit Symmetric | ECC 256bit Auth / AES 128bit Symmetric |
| Auto firmware upgrades of downstream devices | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| Offline Controller Logic                     | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| DIP Switches                                 | 8                                        | 8                                        | 8                                      | 8                                      | 8                                      |
| Run Indicator LED                            | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| Power LED                                    | YES                                      | YES                                      | YES                                    | NO                                     | NO                                     |
| Over-Temperature LED                         | NO                                       | YES                                      | NO                                     | NO                                     | YES                                    |
| PSTN Dialler Support (RS232)                 | YES                                      | YES                                      | NO                                     | NO                                     | YES                                    |
| Tamper Detection                             | YES – Optical via ADCs                   | YES – Optical via ADCs                   | YES – Microswitch                      | YES – Optical via ADCs                 | YES – Optical via ADCs                 |
| USB Expansion Port                           | YES                                      | YES                                      | NO                                     | YES                                    | YES                                    |
| RS232c Serial Port                           | YES                                      | YES                                      | NO                                     | NO                                     | YES                                    |
| Secure Boot                                  | NO                                       | NO                                       | YES 384bit                             | YES 384bit                             | YES 384bit                             |
| External Watchdog Chip                       | YES                                      | YES                                      | NO                                     | NO                                     | NO                                     |
| CPU Internal Watchdog                        | NO                                       | NO                                       | YES                                    | YES                                    | YES                                    |
| Real Time Clock with backup capacitor        | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| Temperature Sensors                          | NO                                       | YES                                      | NO                                     | NO                                     | YES                                    |
| External Voltage Measurement (ADC)           | YES                                      | YES                                      | YES                                    | YES                                    | YES                                    |
| Board ID Resistors (ADC)                     | YES                                      | YES                                      | NO – Variant in OTP                    | NO – Variant in OTP                    | NO – Variant in OTP                    |
| Connector for Plugin Module                  | YES                                      | YES                                      | NO                                     | YES                                    | YES                                    |
| Security Chip                                | NO                                       | AT98 Enhanced VAULTIC HS                 | Edgelock                               | Edgelock                               | FIPS 140-3 approved Edgelock           |
| Temperature Sensing                          | NO                                       | YES                                      | NO                                     | NO                                     | YES                                    |
| In Service Relay                             | NO                                       | YES                                      | NO                                     | NO                                     | YES                                    |
| Key Lengths                                  | P256 & SHA1 Factory / P384 & SHA384 Site | P256 & SHA1 Factory / P384 & SHA384 Site | P384 & SHA384                          | P384 & SHA384                          | P384 & SHA384                          |
| RS485/External Power Overload Fuses          | Polyfuses                                | Polyfuses                                | eFuses (monitored)                     | Polyfuses                              | eFuses                                 |

\*60 when at v9.30 or earlier.\
‡Available from v9.20 onwards.\
†Available from v9.50 onwards.

***

## Field device features comparison

| Field Device Feature            | C6000 Standard                           | C6000 High Sec                           | C7000 Single Door | C7000 Standard                           | C7000 High Sec                           |
| ------------------------------- | ---------------------------------------- | ---------------------------------------- | ----------------- | ---------------------------------------- | ---------------------------------------- |
| Max HBUS Devices per Wiring Run | 80                                       | 80                                       | 80                | 80                                       | 80                                       |
| Max HBUS Wiring Run Length      | 500m                                     | 500m                                     | 500m              | 500m                                     | 500m                                     |
| Star Wiring of Field Devices    | With plugin module, HBUS Hub or OSDP Hub | With plugin module, HBUS Hub or OSDP Hub | NO                | With plugin module, HBUS Hub or OSDP Hub | With plugin module, HBUS Hub or OSDP Hub |
| Daisy Chain Wiring              | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| OSDP Reader Support             | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| Customisable Reader Images      | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| Keypad Triggered Events         | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| Reader Mimic Panel              | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| Custom Messages on Readers      | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| Field Downloadable Code         | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| End-of-Line Encryption Module   | NO                                       | YES                                      | NO                | NO                                       | YES                                      |
| Aperio Support                  | YES                                      | YES                                      | v8.90+            | v8.90+                                   | YES                                      |
| RSI/Schlage RS485 Support       | YES                                      | YES                                      | v8.90+            | v8.90+                                   | YES                                      |
| Moduteq/MBus Support            | YES                                      | YES                                      | YES               | YES                                      | YES                                      |
| GBUS Support                    | YES (v9.10+ NO)                          | YES (v9.10+ NO)                          | NO                | NO                                       | NO                                       |
| Wiegand Support                 | With plugin module or HBUS Door module   | With plugin module or HBUS Door module   | YES               | With plugin module or HBUS Door module   | With plugin module or HBUS Door module   |
| Cardax IV Support               | YES – 8R/4R module                       | YES – 8R/4R module                       | NO                | YES – 8R/4R module                       | YES – 8R/4R module                       |

***

## Supported credential types

| Credential Type    | C6000 Standard | C6000 High Sec | C7000 Single Door | C7000 Standard | C7000 High Sec |
| ------------------ | -------------- | -------------- | ----------------- | -------------- | -------------- |
| MIFARE DESFire     | YES            | YES            | YES               | YES            | YES            |
| MIFARE Classic     | YES            | YES            | YES               | YES            | YES            |
| MIFARE Plus        | YES            | YES            | YES               | YES            | YES            |
| Mobile Credentials | YES            | YES            | YES               | YES            | YES            |
| 125 kHz            | YES            | YES            | YES               | YES            | YES            |
| PIV                | NO             | YES            | NO                | NO             | YES            |
| PIV-I              | NO             | YES            | NO                | NO             | YES            |
| TWIC               | NO             | YES            | NO                | NO             | YES            |
| QR Codes           | YES            | YES            | YES               | YES            | YES            |

***

🔗 **Related**

* [Ethernet Bridge Mode](/knowledge-hub/products/cc-hardware/controllers/controller-7000-and-7000-sdc/configure/controller-7000-ethernet-bridge-mode.md). Bridging is supported on Enhanced and High Sec variants (v9.50+).
* [Ports](/knowledge-hub/products/cc-hardware/controllers/controller-7000-and-7000-sdc/reference/controller-7000-ports.md). The ports the controller uses on the network.
* [Controller 7000](broken://pages/873trKCrdhjXzfqYdsdU). Variants, specifications, and accessories.


---

# Agent Instructions
This documentation is published with GitBook. GitBook is the documentation platform designed so that both humans and AI agents can read, navigate, and reason over technical content effectively. Learn more at gitbook.com.

## Querying This Documentation
If you need additional information that is not directly available in this page, you can query the documentation by asking a question.

Perform an HTTP GET request on the following URL with the `ask` and `goal` query parameters:

```
GET https://help.security.gallagher.com/knowledge-hub/products/cc-hardware/controllers/controller-7000-and-7000-sdc/reference/controller-7000-limits.md?ask=<question>&goal=<user_goal>
```

`ask` is the immediate question: it should be specific, self-contained, and written in natural language.
`goal` is what the user is ultimately trying to achieve, the reason they need the answer. Sharing it helps GitBook give you a better, more relevant answer. A goal is most helpful when it describes the outcome the user wants rather than restating the question. For example, with `ask=how do I create an API token`, a goal like `automate deployments from our CI pipeline` lets GitBook tailor the answer to that use case.

The response will contain a direct answer to the question and relevant excerpts and sources from the documentation.

Use this mechanism when the answer is not explicitly present in the current page, you need clarification or additional context, or you want to retrieve related documentation sections.