Ferrite Choke

Identify the ferrite choke requirements for Controller 7000 installation and operation.

With the initial release of the 7000 controller range, a ferrite choke was supplied with each controller.


Purpose

The ferrite choke is installed on the network cable to the controller, as close as possible to the network port on the C7000.

It is required to allow the 7000 controller range to meet EN 50130-4 compliance (electromagnetic compatibility for alarm systems).


Future removal

The ferrite choke requirement will be removed in future hardware revisions of the controller when Gallagher re-submits for EMC testing.


When the ferrite choke can be omitted

The ferrite choke can be omitted if:

  • The site does not require network devices to be compliant with EN 50130-4, and

  • The controllers are not installed in a noisy EMF (electromagnetic field) environment.

Installer note: If EN 50130-4 compliance is required at the site, the ferrite choke must be installed as supplied. If the site has no such requirement and is in a low-EMF environment, the ferrite choke is optional.