Test controller connections

Test Controller 6000 network connectivity, server communication, port 1072, and diagnostics.

The majority of testing on this page is best done from the Controller network connection point using a laptop, back to the server. From v9.30 onwards the controller is capable of performing this function itself (see Network Connectivity Tools below).

Ideally the laptop would be configured the same as the Controller being tested and plugged into the same network connection point.

⚠️ From CC v8.50 onwards the controller is the device that makes the initial TCP connection to the server. The server does not send any TCP connection request to the controller.


Ping

C:\>ping <controller IPAddress>
C:\>ping <server IPAddress>

If a reply is received, this proves there is a network connection to the controller or server. It also adds an entry to the ARP cache (required before running ARP).

May fail if:

  • No route to the controller.

  • The site network is configured to disable ICMP (which ping uses).

  • Ping traffic is specifically blocked.

Also check the Link Light at the Ethernet connection of the controller. The green LED next to the Ethernet adapter should be on solid.

💡 If ping returns an IPv6 address but you want IPv4, use the -4 switch: C:\>ping -4 <HostName>

💡 If the controller is on a different subnet to the server, the switch the controller is plugged into must reply to pings. The controller pings the gateway to ensure a connection before transmitting data to the server.


Listen Port

By default the port controllers communicate on is Port 1072. This is defined as the Listen Port in the Gallagher Registry.

Unless you have a specific reason for setting a unique Listen Port, 1072 is used on installing Command Centre.

⚠️ If the site is using a non-standard listen port, the controller must first connect to the server to pick up the custom communication port.


Telnet

Tests TCP Port 1072 (used for controller-server and controller-controller communication). Must be run in both directions.

⚠️ From v8.50 upwards, controllers communicate only outbound to the server on the Listen Port (1072 by default). The server no longer reaches out to the controller.

If you get "'telnet' is not recognized as an internal or external command...", install Telnet from Turn Windows features on or off in Control Panel, Programs and Features. Install both Telnet Client and Telnet Server.

Indications:

  • OK (1): Screen blanks; cursor stays flashing top-left. The port is open.

  • OK (2): Cursor returns to C: prompt. The port is open (you may also see "connection lost"; it may also raise an alarm if the controller is online).

  • FAIL: Port is blocked. Check: (1) Firewall, (2) Switch/router IT policy, (3) Anti-virus (some anti-virus prevents controller connections, disable temporarily to test).


Telnet alternative - Test-NetConnection (TNC)

  1. Open PowerShell (Admin privileges not required).

  2. Run:

Advantages over Telnet:

  1. You do not have to install the Telnet client on Windows machines.

  2. You can check the Server IP address and Network Adaptor used to communicate with the Controllers or target device.


Network Connectivity Tools (firmware v9.30+)

Available from controller firmware v9.30 onwards.

From within the controller's web pages (Web Config and Debug pages) there is a utility link called Network connectivity tools. By default it has the default Gallagher Controller Service listen port, 1072.

  1. Enter the Server's IP address into the Address window.

  2. Click ConnectToIPAddress.

On the C6000 the tool is launched from the controller's web pages (Web Config / Debug):

Network connectivity tools as launched from the C6000 controller web pages
Network Connectivity Tools landing page

A successful connectivity check result:

Network connectivity tools - successful connectivity check result

A failed check (server not reachable on the port):

Network connectivity tools - failed connectivity check result

There is also a link to this utility on the Debug main page of the controller:

Network connectivity tools link under the C6000 Debug menu

ARP

After pinging the controller, run ARP to ensure you are receiving a reply from an actual controller. Look for the Internet Address you pinged above.

If the Physical Address starts with 00-90-1d, it is a Gallagher controller.


netstat

Results on CC v8.40 and below

  • Two established connections:

    • Item A: controller connected to server through TCP port 1072.

    • Item B: server connected to controller on TCP port 1072.

netstat result on CC v8.40 and below showing two established connections

Network routing should be discussed and checked with the network administrator if controllers are not reporting back.

Results on CC v8.50 and above

  • Only one connection established (outbound from controller). This is due to the controller services change implemented in v8.50.

netstat result on CC v8.50 and above showing single outbound connection

Server with port 1072 listening for Controller service

The server is listening on port 1072, used by a 'service' with a PID.

netstat -ano output showing port 1072 and associated PID

Confirm via Windows Task Manager that the PID is used by the 'FT Controller Service'.

Windows Task Manager PID list confirming FT Controller Service PID

⚠️ PID mismatch: If the PID using port 1072 does not match the PID of 'FT Controller Service', another application or service is using (locking) port 1072, causing the controller not to come online.

Two options:

  1. Get the third-party application to change or stop using port 1072.

  2. Change the listen port of the server-controller communication to a custom port.

netstat -ano showing unknown process holding port 1072

Web Browsing

If a controller is not coming online, web-browse the controller to confirm what IP configuration it is using.

To web-browse: enter the controller's IP address followed by /config. in the address bar. Note the trailing full stop, which is required.

A logon prompt appears:

Username
Password (controller state)

diagnostic

CardaxFT if controller is in 2-flash state

diagnostic

CardaxFTxxxx if controller is in 1-flash state (site-specific value based on the Site Serial number - Authorized Channel Partners can contact Tech Support)

diagnostic

A configured password if running CC v8.40 or later

Key debug pages

Page
What it tells you

TCPSender

Primary page for confirming TCP IP settings. The main item to check is the Server IP. If it doesn't match the actual Server IP, the controller will not come online. Active sessions show if the server is connected to the controller.

TCPExchange

Confirm keys and certificates are OK. Confirm the correct Master certificate is selected (should match the Certificate setting in the Controller/Setup tab). Active sessions show if the controller is connected to the server.

Errorlog

Shows problems with the controller or connectivity issues. Check as a last resort.

Node Number

Must match the node number in Command Centre. To view the node number in CC: open Controller Properties > Setup tab, hold Ctrl and double-click in a clear area of the Setup tab. A popup window shows the Node number.

Additional testing screenshot 6