Shutdown codes
Reference Controller 6000 shutdown codes and their causes.
Looking through a controller's error log (using the web browser to connect, see Testing Controller Connections), every time a controller shuts down there is an SC descriptor with a number.
These codes can also be seen in alarm messages in Command Centre after a controller restarts.
Shutdown code reference
0
Normal Termination (debug)
Normal
—
1
Remote Reset Request
Normal
Reset request after doing a code download
2
Power Fail
Normal
Power has failed
3
Hardware watchdog timeout
Software or hardware fault
S/W or H/W fault
4
Startup Failed
Software fault
Corrupt version of controller S/W
5
Configuration Failed
Fault
Invalid configuration
6
Out of Memory
Fault
S/W bug, or just too much going on
7
Assertion
Fault
S/W bug, should only occur in debug versions
8
RAM error
Hardware fault
Faulty RAM chip
9
Code checksum error
Fault
Controller code has been corrupted
10
FTP server running
Normal
Controller was started with the /FTP parameter
11
Uncaught exception
Software fault
Depends on the exception
12
Caught exception
Software fault
Depends on the exception
255
Undefined Fault
Fault
Almost anything