Run LED and DIP switches
Reference Controller 6000 Run LED patterns and DIP switch functions.
Run LED diagnostic indications
The red Run LED (D9) flashes to indicate the operating status of the Controller.
Slow
2000 ms on, 1000 ms off
Controller is searching for software FTS files
Fast
130 ms on, 130 ms off (4 Hz)
Initialising
1 Flash
500 ms on, 500 ms off (1 Hz)
Normal running
2 Flash
2 flashes then pause (each flash 50 ms on, 400 ms off, 1.2 s pause)
Controller has an IP but no configuration, or has been configured incorrectly
3 Flash
3 flashes then pause
Controller requires an IP address. Ensure BootP Service (CCFTBPS.exe) is running, the Controller is configured correctly, and connected to the network
4 Flash
4 flashes then pause
No private key or certificate loaded. Note: this state can only be reset by the factory of manufacture
5 Flash
5 flashes then pause
Invalid private key or certificate loaded, or key and certificate do not match the Controller serial number. See DIP Switch 8 Recovery or seek Gallagher Tech Support advice
6 Flash
6 flashes then pause
The Controller has dropped its code. See DIP Switch 8 Recovery or seek Gallagher Tech Support advice
7 Flash
7 flashes then pause
A USB-stick software upgrade is complete and the USB drive must be removed for installation to complete
Controller Resetting
450 ms on, 50 ms off (2 Hz)
Controller resetting
Short flash + long flash (1 s cycle)
100 ms on, 250 ms off
Boot code monitor running, network unplugged
DIP switch settings
Default settings are in bold:
DS1
ON / OFF
Controller will accept WWW connections / Controller will reject WWW connections
DS2
ON / OFF
Initialise. On startup all site-specific data including configuration, site encryption keys and events are securely removed. The Controller uses DHCP (with a DHCP server) or BootP (with Command Centre server) to get a new IP address. / Normal startup, configuration retained
DS3
ON / OFF
When DS2 is ON in conjunction with DS3, the Controller uses the default IP address configuration / Controller will wait for IP configuration depending on DS2 setting
DS4
ON / OFF
Controller will reject IP address offers from standard DHCP servers. Switch ON if using Command Centre's BootP Service to configure IP and a DHCP server is also present on the network. OFF = Controller will accept DHCP offers. ⚠️ DS4 must be OFF for Controllers running pre-v8.90 firmware, otherwise the Controller will not work correctly
DS5
ON / OFF
For factory testing only / On startup, the main application is run
DS6
OFF
Unused
DS7
OFF
Unused
DS8
OFF / ON
Boot normally / Revert to the factory default version of the operating system. In conjunction with DIP Switch 2, revert to the factory default version of the software, similar to a factory reset (all configuration, events and alarms will be lost). See DIP Switch 8 Recovery and document 3E3438 Leaflet Controller 6000 DIP switch 8 Recovery. ⚠️ A DIP switch 8 factory reset on a v8.20 or later Controller will not revert it back to v8.10 or earlier. ⚠️ Only turn DS8 on when the Controller has failed (firmware corruption or recovery). Do not use it routinely
Quick reference
DS1+DS2+DS3 ON - Default IP web-config addressing (
192.168.1.199/config.)DS2 ON, others OFF - BootP request (controller broadcasts for IP)
DS2+DS8 ON - DIP Switch 8 Recovery procedure. Only when the Controller has failed (see DIP Switch 8 Recovery)
All OFF - Normal operation (use existing pinned configuration)
For shutdown codes after a controller restart, see Shutdown Codes.
🔗 Related
Shutdown Codes. The SC codes seen in the error log and alarms.
DIP Switch 8 Recovery. The DS2+DS8 recovery procedure.
Run LED Diagnostics and Shutdown Codes. The shared C6000/C7000 diagnostics reference.