For the complete documentation index, see llms.txt. This page is also available as Markdown.

NAND issue

Diagnose Controller 6000 NAND storage failures and identify the required recovery action.

⚠️ Affects controllers manufactured 2011 to 2015 only. The fix only needs to be applied once to each affected controller. Resolved in firmware v7.30 and above.

Background

Between 2011 and 2015 the Gallagher repairs department were seeing a significant number of instances where Controller 6000s were coming back for repairs.

The cause turned out to be that the NAND flash RAM on the 6000 was being addressed incorrectly due to a manufacturing change by the supplier of the NAND chip.

Fix

In v7.30 a new firmware was released to fix these issues during a firmware update. This is reflected in the release note of v7.30 (and later versions of Command Centre).

Other firmware versions with the fix for older versions of Command Centre were also released:

Firmware version
For Command Centre version

vGR6.01.92

6.01-era systems

vGR7.10.401

7.10-era systems

vGR7.20.685

7.20-era systems

These are available from the Gallagher File Transfer Site, in the Controller Software > 6000NANDFix folder.

If a system is 7.05 or earlier, download vGR6.01.92 from the Gallagher File Transfer Site, add it to the Device Software as a 6000 firmware, then downgrade the controller to the older firmware, wait for the firmware to do its work (approximately 9.5 minutes), and when it is online again, upgrade to the original firmware.


Which controllers are affected

Range type
Affected range
Affected MAC range

Serial number

1120xxxxxx to 1508xxxxxx

00:B2:6D to 01:38:AC

How to check if the fix has been applied

Run the FT Support Tool on a server to list controllers and show the WinCE version. If the WinCE build version (Software Type 1) is v2.00/b22 or higher, the fix has been applied.

Example FT Support Tool output:

Device
Software Type
Assigned Version
Installed Version
ItemType
Description

Controller 6000

0

vGR6.02b33

v6.02//b33

Controller Grover

Controller Software Version

Controller 6000

1

v1.00//b85

Controller Grover

WinCE build, check this

Controller 6000

2

v1.01//b6016

Controller Grover

Bootloader Version

Controller 6000

3

v1.02//b0

Controller Grover

Plugin Version

Controller 6000

4

v1.00//b25

Controller Grover

(In this example, Software Type 1 is v1.00//b85, which needs upgrading to v2.00/b22+.)


Risks of not doing the upgrade

⚠️ The issue is not detectable before the problem occurs. A controller that has been running for years could have the problem, but the controller only has a chance of failing when it restarts.

If you decide not to do the upgrade, you run a real risk that every time the controller 6000 restarts, it could render the controller unusable. The DIP Switch 8 procedure will not fix this.

Applying the fix will resolve this issue, but the controller patch is applied during the power up cycle. If the controller experiences the NAND issue during this initial restart, the controller will be unusable on restart. When doing the upgrade, have spare controllers on hand in case some fail during the patch.