I2C Bus Not Responding

Diagnose and resolve Controller 6000 I2C bus communication failures before upgrading.

The 6000 controllers feature three Supercaps on the board, designed to keep the processor operational while the controller powers down.

Symptom

Field
Value

Error

I2C Bus not responding (in event viewer and alarm viewer)

Log Location

Event Viewer / Alarm Viewer

Source

Command Centre Event Viewer

Affected version

All

Cause

If the I2C Bus alarm or event appears in Command Centre, it likely indicates that the Supercaps on the controller have leaked, which affects the Bus chip.

This issue has been known to cause additional problems, especially in controllers that have been upgraded to the Linux version.

Resolution

⚠️ Hardware fault, not a software fix. Return the controller to repair, or replace the controller.

Before upgrading a site of C6000 controllers from WinCE to Linux, check the Command Centre alarm log for "I2C Bus not responding" messages. Controllers with this fault should be replaced before the WinCE to Linux upgrade, as they have been known to cause issues during upgrade. See Upgrading, Downgrading, Defaulting and Compatibility for the upgrade-prep checklist.