High Sec Specific Information
Understand Controller 6000 High Sec variants, naming, features, and compatibility.
This page covers content specific to the C6000 Enhanced (C300101) and High Sec (C305101) controllers. These items are not applicable to the standard C6000.
Naming change (2023)
In 2023 the naming convention of the 6000 Enhanced/PIV controllers changed:
Controller 6000 High Spec
Controller 6000 Enhanced
Controller 6000 (HS) PIV
High Sec Controller 6000
Customer documentation and old screenshots may still use the original names. Confirm which physical controller is on site (C300101 is Enhanced; C305101 is High Sec) before recommending a procedure.
High Sec and Enhanced controller temperature limits
The 6000 High Sec and Enhanced controllers have internal temperature monitors that limit the maximum and minimum operating temperatures they will operate at.
High temperature
78 °C
Controller generates an abnormal temperature warning
80 °C
Power to the controller is shut down; an orange LED beside the power LED illuminates
Stays shut down until...
Temperature drops below the 78 °C threshold
Low temperature
-11 °C
Controller generates an abnormal temperature warning
-13 °C
Power to the controller is shut down; an orange LED beside the power LED illuminates
Stays shut down until...
Temperature rises above the -11 °C threshold
Unable to bring a 6000 HS online (Dip Switch 8 issue)
⚠️ Scope: This only relates to WinCE versions of the 6000 HS released prior to July 2022 (HS controllers with serial number 2225xxxxxx and below).
If you have been upgrading a 6000 High Spec / Enhanced controller (C300101) and had issues with bringing it online or upgraded, and have performed a DIP Switch 8 procedure on the controller, you may be running into a known issue.
Symptom
If a 6000 HS controller has been upgraded directly from v7.50 (or earlier) to v8.10 and then had a DIP Switch 8 procedure performed, the controller becomes unusable and will have to be returned to Gallagher for servicing before it will be usable again.
Indicators:
The C6000 HS will take an IP address.
The controller shows an inbound connection on the TCP Sender page (web-browse).
On TCP Exchange there is no outbound connection.
Command Centre log error:
⚠️ Unrecoverable in the field. Must be sent back to Gallagher for repair.
Prevention - recommended upgrade procedure
The Controller 6000 HS (C300101 Enhanced) with version 7.50 and below should be upgraded first to any version within the range v7.60 to v8.00.
This ensures the controllers will not brick once upgraded to v8.10 and the DIP Switch 8 procedure is performed.
See also DIP Switch 8 Recovery and Unable to Bring a 6000 HS Online.
Controller 6000 - High Spec or PIV Addressing (v8.00 / v8.10 only)
⚠️ Scope: This issue only happens at firmware versions v8.00 and v8.10. Linux Controllers (v8.20+) are not affected.
At v8.00 and v8.10, the Controller 6000 Enhanced and High Sec controllers behave differently than the standard 6000 controller with respect to setting the IP address of the controller via web browser.
Both controllers have 1GB Dual Failover network interfaces.
Symptom
If you are trying to web-browse to the controller with DIP switches 1, 2, 3 turned ON to connect to the default IP 192.168.1.199, and you cannot connect or ping, the controller may be having issues with the network interface of the device it is connected to.
Likely failure modes: the connection speed of the network interface (laptop or switch port) is 1 GB or 100 MB.
Workaround
Change the network interface speed to 10 MB.
Connect to the controller and complete addressing.
After addressing, the speed can be returned to Auto Negotiation again.

🔗 Related
DIP Switch 8 Recovery. The recovery procedure and the High Spec brick warning.
Unable to Bring a 6000 HS Online. The related brick scenario in detail.
High Spec or PIV Addressing. The addressing workaround as a standalone page.