Upgrading WinCE to Linux
Migrate a Windows CE Controller 6000 to Linux firmware.
This page covers all three WinCE-to-Linux upgrade methods. Each method has its own dedicated page with the method-specific detail and process flow.
The three upgrade methods
Default IP
BootP unavailable, for example controller and server on different subnets
BootP
Controller and server on the same subnet, no DHCP server
For controller-side IP assignment (Method 1/2/3), see Assigning a Controller an IP address.
Process diagrams
DHCP - site network has a DHCP server:

Default IP - BootP unavailable (controller and server on different subnets):

BootP - controller and server on the same subnet, no DHCP server:

Common to all three methods
⚠️ Two-step migration path: Controllers upgrade to v8.10 WinCE first, then to the Linux version. This is the only supported path. See FAQs - Upgrading Factory WinCE Controller 6000s, Q1.
⚠️ DIP Switch differences: WinCE OS (v8.10 or older) requires DIP Switch 2 AND 3 ON for DHCP. Linux OS (v8.20 or later) only requires DIP Switch 2 ON. Turn OFF DS3 when the "Dip Switch 3 must be OFF" alarm fires after upgrade to v8.10, otherwise the Controller cannot be upgraded beyond v8.10.
⚠️ Keep DIP Switch 2 ON until the controller matches the CC version: breaking-compatibility changes introduced in v8.40 mean the server cannot push configuration changes to a controller that has not yet been upgraded to match the Command Centre version. Keep DS2 ON until the upgrade is complete.
⚠️ Software selection: Leave None Selected in the Controller Software dropdown until the controller has connected. The controller will restart a number of times. Don't change the software settings while it's upgrading.
⚠️ Revalidate Certificate may be required if DIP Switch 2 was ON during the upgrade. See Revalidate Certificate.
After the upgrade
Turn OFF all DIP Switches once the controller has its IP address set (unless the site uses BootP and a future restart will need it).
Verify the firmware version on the Controller properties.
Push configuration to the controller.
For the full upgrade and downgrade matrix and compatibility rules, see Upgrading, Downgrading, Defaulting and Compatibility.
🔗 Related
Upgrading WinCE Controllers using DHCP. The DHCP method.
Upgrading WinCE Controllers using Default IP. The Default IP method.
Upgrading WinCE Controllers using BootP. The BootP method.