Upgrading WinCE to Linux

Migrate a Windows CE Controller 6000 to Linux firmware.

This page covers all three WinCE-to-Linux upgrade methods. Each method has its own dedicated page with the method-specific detail and process flow.

The three upgrade methods

Method
When to use
Detail page

DHCP

Site network has a DHCP server

Default IP

BootP unavailable, for example controller and server on different subnets

BootP

Controller and server on the same subnet, no DHCP server

For controller-side IP assignment (Method 1/2/3), see Assigning a Controller an IP address.

Process diagrams

DHCP - site network has a DHCP server:

WinCE to Linux upgrade via DHCP - process diagram

Default IP - BootP unavailable (controller and server on different subnets):

WinCE to Linux upgrade via Default IP - process diagram

BootP - controller and server on the same subnet, no DHCP server:

WinCE to Linux upgrade via BootP - process diagram

Common to all three methods

⚠️ Two-step migration path: Controllers upgrade to v8.10 WinCE first, then to the Linux version. This is the only supported path. See FAQs - Upgrading Factory WinCE Controller 6000s, Q1.

⚠️ DIP Switch differences: WinCE OS (v8.10 or older) requires DIP Switch 2 AND 3 ON for DHCP. Linux OS (v8.20 or later) only requires DIP Switch 2 ON. Turn OFF DS3 when the "Dip Switch 3 must be OFF" alarm fires after upgrade to v8.10, otherwise the Controller cannot be upgraded beyond v8.10.

⚠️ Keep DIP Switch 2 ON until the controller matches the CC version: breaking-compatibility changes introduced in v8.40 mean the server cannot push configuration changes to a controller that has not yet been upgraded to match the Command Centre version. Keep DS2 ON until the upgrade is complete.

⚠️ Software selection: Leave None Selected in the Controller Software dropdown until the controller has connected. The controller will restart a number of times. Don't change the software settings while it's upgrading.

⚠️ Revalidate Certificate may be required if DIP Switch 2 was ON during the upgrade. See Revalidate Certificate.


After the upgrade

  • Turn OFF all DIP Switches once the controller has its IP address set (unless the site uses BootP and a future restart will need it).

  • Verify the firmware version on the Controller properties.

  • Push configuration to the controller.

For the full upgrade and downgrade matrix and compatibility rules, see Upgrading, Downgrading, Defaulting and Compatibility.