Upgrading WinCE Controllers using BootP
Upgrade a Windows CE Controller 6000 using BootP addressing.
⚠️ Scope: This page is for WinCE 6000 controllers. Linux 6000 controllers do not follow this upgrade path.
When Controllers are brought online using BootP, they get issued a temporary IP to communicate to the Command Centre Server, but do not cache information. The server cannot send down configuration changes due to major changes breaking compatibility in v8.40.
This creates the need to keep DIP Switch 2 ON until the Controller has been upgraded to match the Command Centre version.
⚠️ BootP requires same subnet: BootP can only be used where the Controller and Command Centre are both on the same subnet. Broadcast traffic does not cross subnet boundaries by default.
Certificate behaviour with DIP Switch 2 ON
⚠️ When DIP Switch 2 is ON, the Controller drops its configuration, including the pinned certificate. When the Controller connects to the server after restart, the certificate will not match the server. This causes the Controller to remain offline and generate an 'Authentication of [Controller] failed - invalid certificate' alarm in Command Centre.
A 'Revalidate certificate' override is required to bring the Controller online after a restart with DIP Switch 2 ON.
Process flow
The general sequence for getting a factory Controller upgraded to the latest release version using BootP:

Ensure the "FT Bootstrap Protocol Service" is running on the Command Centre server.
Set DIP Switch 2 ON on the controller.
Power on the controller. It will broadcast for an IP at the 3-flash state.
The FT Bootstrap Protocol Service replies with controller configuration including the server IP.
The controller connects to the server using the BootP-assigned IP.
Command Centre upgrades the Controller through the upgrade path.
After the Controller upgrade completes, apply the Revalidate Certificate override if alarms fire.
For method-by-method addressing detail, see Assigning a Controller an IP address (Method 1 BootP, Method 3 ccftBootp.exe).
For the full WinCE-to-Linux composite covering BootP, DHCP and Default IP, see Upgrading WinCE to Linux.