High Spec or PIV Addressing
Configure addressing for Controller 6000 Enhanced and High Sec PIV variants.
This page covers the addressing behaviour of the C300101 (Enhanced) and C305101 (High Sec) controllers at firmware v8.00 and v8.10, including the network-interface speed workaround. The same content is covered in context on the High Sec Specific Information page.
⚠️ Scope: This issue only happens at firmware versions v8.00 and v8.10. Linux Controllers (v8.20+) are not affected.
At v8.00 and v8.10, the Controller 6000 Enhanced and High Sec controllers behave differently than the standard 6000 controller with respect to setting the IP address of the controller via web browser.
Both controllers have 1GB Dual Failover network interfaces.
Symptom
If you are trying to web-browse to the controller with DIP switches 1, 2, 3 turned ON to connect to the default IP 192.168.1.199, and you cannot connect or ping, the controller may be having issues with the network interface of the device it is connected to.
Likely failure modes: the connection speed of the network interface (laptop or switch port) is 1 GB or 100 MB.
Workaround
Change the network interface speed to 10 MB.
Connect to the controller and complete addressing.
After addressing, the speed can be returned to Auto Negotiation again.

🔗 Related
High Sec Specific Information. The full Enhanced and High Sec reference.
Assigning a Controller an IP address. The standard addressing procedure.
Last updated
Was this helpful?