FAQs - Upgrading Factory WinCE Controller 6000s

Upgrade factory Controller 6000 units from Windows CE to Linux and resolve migration questions.

Frequently asked questions about upgrading factory WinCE Controller 6000s.


Frequently Asked Questions

Q1. Why does the Controller upgrade to v8.10 before migrating to Linux OS?

Factory Controllers go through a two-step migration process. First, they get upgraded to v8.10 Controller software where they download necessary files for Linux migration.


Q2. Why do I have to revalidate the certificate after a Controller restarts following the use of Dip Switch 2?

When Dip Switch 2 is ON, the Controller will drop its configuration which includes the pinned certificate. When the Controller connects to the server after the restart, the certificate will not match the server, causing the Controller to remain offline and generate an 'Authentication of [Controller] failed - invalid certificate' alarm in Command Centre. Therefore a 'Revalidate certificate' override is required to bring the Controller online after a restart with Dip Switch 2 ON.


Q3. Why do Controllers restart after a time zone change?

Time Zone changes do not dynamically update in all Linux OS driver modules, thereby requiring a Controller restart to take effect across the entire system.


Factory firmware shipping versions

To make it easier for sites to bring controllers online to supported versions of Command Centre, Gallagher has released controllers from the factory with later firmware versions:

Date
What ships from factory

From 30 June 2022

6000 controllers ship with Linux OS

From 30 June 2022

Firmware v8.20 installed on 6000s

From 18 August 2023

Firmware v8.90 installed on 6000s