For the complete documentation index, see llms.txt. This page is also available as Markdown.

Bring a controller online and configure networking

Bring a Controller 6000 online and configure its server connection, networking, and diagnostics.

Getting a Controller 6000 onto the network and talking to the Command Centre server. This page pulls the workflow together. The dedicated topic pages are the canonical references for each step.

IP address assignment

For the full procedure (Methods 1 to 3: BootP, Default IP, ccftBootp.exe), see Assigning a Controller an IP address.

⚠️ From Command Centre v8.50 onwards there is only an outbound TCP connection from the Controller to the Server. Controller to Port 1072 to Server.


Trouble bringing a controller online

If the Server has more than one network interface, ensure that the Use different IP for Server field has the IP address for the network interface that is connecting to the controllers.

6000 Linux-specific points

  • When the controller first comes online, ensure the software selected is left as None Selected until the controller has connected.

  • The controller will restart a number of times. Don't change the software settings while it's upgrading.

  • The upgrade process involves Command Centre upgrading the controller to 8.10 WinCE first, then upgrading to the Linux version.

⚠️ DIP Switch 2: During the upgrade process, DIP Switch 2 should remain ON if using the BootP addressing option.

  • If the site has to assign IP addresses using the DIP Switch 1, 2, 3 procedure, once the controller has its IP address set, turn OFF all DIP Switches.

  • Upgrading via USB is an alternative upgrade option (see the release notes for your version of Command Centre for the correct procedure).

For controller-drops-offline behaviour after first connection, see Controller Drops Offline Immediately After Coming Online.

For server-side multi-NIC behaviour, see Command Centre Server has Multiple Network Adaptors.


Testing controller network connections

The majority of testing is best done from the Controller network connection point using a laptop, back to the server.

⚠️ From CC v8.50 onwards the controller is the device that makes the initial TCP connection to the server. The server does not send any TCP connection request to the controller.

For the full testing toolset (Network Connectivity Tools, Ping, Listen Port, Telnet, TNC, ARP, netstat, Web Browsing, Node Number), see Testing Controller Connections.

Key testing tools (summary):

Tool
Use

Network Connectivity Tools (firmware 9.30+)

Web-browse to controller at {IP}/debug., use credentials provided by Tech Support. Tests outbound connectivity from the controller.

ping <controller IP> / ping <server IP>

Confirms basic network connection. Use -4 switch to force IPv4.

telnet <controller IP> 1072

Tests TCP Port 1072 (controller-server communication). Run in both directions. Indication of blocked port means check firewall, switch/router, anti-virus.

tnc <ip> -p <port> (PowerShell)

Modern alternative to telnet. Confirms outbound port and server IP.

arp -a

Physical Address starting with 00-90-1d is a Gallagher controller.

netstat -an / -ano

CC v8.40 and below: two established connections (inbound and outbound on 1072). CC v8.50 and above: one outbound connection.

⚠️ PID mismatch on port 1072: If the PID using port 1072 does not match the PID of 'FT Controller Service' in Task Manager, another application is locking port 1072. Two options: (1) get the third-party app to change port, (2) change Command Centre's listen port.

Web Browsing ({controller IP}/debug.):

Condition
Logon
Password

Controller in 2-flash state

diagnostic

[REDACTED] (default - contact Tech Support)

Controller in 1-flash state

diagnostic

[REDACTED] (site-specific value based on Site Serial number - contact Tech Support)

CC v8.40+

diagnostic

May be a configured password, check with Tech Support

Key pages on the controller's debug web interface:

  • TCPSender. Confirm TCP IP settings. Check Server IP matches the actual Server IP.

  • TCPExchange. Confirm keys and certificates are OK and the correct Master certificate is selected.

  • Errorlog. Shows recurring errors or restarts. Check as a last resort.

  • Node Number. Must match the node number in Command Centre. To view the CC node number: open Controller Properties > Setup tab, then Ctrl + double-click in a clear area of the Setup tab. A popup window shows the node number.


Firewall configuration

For the full firewall configuration procedure, see Firewall Issues.


DNS - Dynamic DNS

For DNS failover behaviour and configuration, see Dynamic DNS.


🔗 Related

Last updated

Was this helpful?