Secondary Power Supplies

When powering Gallagher devices from a secondary power supply, other than the one powering the controller.

The three common connections

When wiring Gallagher devices (HBUS, GBUS, Local BUS and Cardax IV) there are 3 connections that simply must be common to the controller they are connected to:

  • A and B for the buses

  • White and Blue wires for Cardax IV

  • Last but not least, the 0 V or ground (Black) wires

Power can be supplied via a 2nd local Gallagher power supply, or a 3rd party power supply.

⚠️ The grounds must be common (connected) in this case, whichever power supply is used.

The RS485 grounding rule

The 485 BUS is an international standard that requires the Ground to be present.

In some circumstances the bus will work with no ground, but that is only because the 485 devices are at almost the same common reference voltage level (ground) and appear to work. However, when that changes, the communications will become intermittent and unreliable. This is one of the most common problems with Fence Controllers.

⚠️ Chasing intermittent fence controller comms? Check the ground bond first, before biasing or termination.

Wiring examples

In the image below, power for the Controller, the 8 In 2 Out Door Module on the left, and the T11 reader is supplied by the power supply on the left. The power for the 8 In 2 Out Door Module on the right and the T20 is supplied from the power supply on the right.

Separate power supplies, wiring example 1

The common item between the two power systems is the ground, and this must be present to have reliable communications.

You can substitute the T20 for a 3rd party reader and, as long as the 8 In 2 Out Door Module is a 4 In 2 Out Door Module Wiegand variant, it will work the same. This is another example of the requirement of the common 0 V connection.

Separate power supplies, wiring example 2

A common mistake

Another common mistake is to think that the Fence Controllers require only the A and B connections. This is a mistake that is very common. The RS485 standard requires a common ground for the serial interface to work reliably.

Separate power supplies, wiring example 3